Kabeltverrsnitt for 475 Ampere ved 600 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 475 A over 600 m ved 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 8.8V (2.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 43.56V (10.89%)
Voltage at Load391.2 VLine Loss: 7242.6 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7042.52 V (1760.63%)0.0 V11616.86 V (2904.22%)5794050.0 WDrop High
2.5 mm²24 A18 A4225.51 V (1056.38%)0.0 V6970.12 V (1742.53%)3476430.0 WDrop High
4 mm²32 A25 A2640.94 V (660.24%)0.0 V4356.32 V (1089.08%)2172768.8 WDrop High
6 mm²41 A32 A1760.63 V (440.16%)0.0 V2904.22 V (726.05%)1448512.5 WDrop High
10 mm²57 A44 A1056.38 V (264.09%)0.0 V1742.53 V (435.63%)869107.5 WDrop High
16 mm²76 A59 A660.24 V (165.06%)0.0 V1089.08 V (272.27%)543192.2 WDrop High
25 mm²101 A78 A422.55 V (105.64%)0.0 V697.01 V (174.25%)347643.0 WDrop High
35 mm²125 A97 A301.82 V (75.46%)98.2 V497.87 V (124.47%)248316.4 WDrop High
50 mm²151 A118 A211.28 V (52.82%)188.7 V348.51 V (87.13%)173821.5 WDrop High
70 mm²192 A150 A150.91 V (37.73%)249.1 V248.93 V (62.23%)124158.2 WDrop High
95 mm²232 A181 A111.2 V (27.8%)288.8 V183.42 V (45.86%)91485.0 WDrop High
120 mm²269 A210 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
150 mm²309 A241 A70.43 V (17.61%)329.6 V116.17 V (29.04%)57940.5 WDrop High
185 mm²353 A275 A57.1 V (14.28%)342.9 V94.19 V (23.55%)46978.8 WDrop High
240 mm²415 A324 A44.02 V (11.0%)356.0 V72.61 V (18.15%)36212.8 WDrop High
300 mm²477 A372 A35.21 V (8.8%)364.8 V58.08 V (14.52%)28970.2 WDrop High
400 mm²570 A445 A26.41 V (6.6%)373.6 V43.56 V (10.89%)21727.7 WDrop High

FAQ — Kabeltverrsnitt for 475 Ampere ved 600 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 475A over 600 meter (400V)?

Etter NEK 400 anbefales 3× 400 mm² kobberkabel for 475A ved 600 meter (400V), som gir et spenningsfall på 8.8V (2.2%).

Hvor mange kW tåler 475A ved 400V?

Kursen leverer opptil 329.09 kW med 500A vern.