Kabeltverrsnitt for 50 Ampere ved 150 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 50 A over 150 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 9.17V (2.29%)
Voltage at Load388.9 VLine Loss: 963.0 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A185.33 V (46.33%)214.7 V305.71 V (76.43%)16050.0 WDrop High
2.5 mm²24 A18 A111.2 V (27.8%)288.8 V183.42 V (45.86%)9630.0 WDrop High
4 mm²32 A25 A69.5 V (17.37%)330.5 V114.64 V (28.66%)6018.8 WDrop High
6 mm²41 A32 A46.33 V (11.58%)353.7 V76.43 V (19.11%)4012.5 WDrop High
10 mm²57 A44 A27.8 V (6.95%)372.2 V45.86 V (11.46%)2407.5 WDrop High
16 mm²76 A59 A17.37 V (4.34%)382.6 V28.66 V (7.17%)1504.7 W~ ≤5%
25 mm²101 A78 A11.12 V (2.78%)388.9 V18.34 V (4.59%)963.0 W✓ OK (≤3%)
35 mm²125 A97 A7.94 V (1.99%)392.1 V13.1 V (3.28%)687.9 W✓ OK (≤3%)
50 mm²151 A118 A5.56 V (1.39%)394.4 V9.17 V (2.29%)481.5 W✓ OK (≤3%)
70 mm²192 A150 A3.97 V (0.99%)396.0 V6.55 V (1.64%)343.9 W✓ OK (≤3%)
95 mm²232 A181 A2.93 V (0.73%)397.1 V4.83 V (1.21%)253.4 W✓ OK (≤3%)
120 mm²269 A210 A2.32 V (0.58%)397.7 V3.82 V (0.96%)200.6 W✓ OK (≤3%)
150 mm²309 A241 A1.85 V (0.46%)398.1 V3.06 V (0.76%)160.5 W✓ OK (≤3%)
185 mm²353 A275 A1.5 V (0.38%)398.5 V2.48 V (0.62%)130.1 W✓ OK (≤3%)
240 mm²415 A324 A1.16 V (0.29%)398.8 V1.91 V (0.48%)100.3 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.23%)399.1 V1.53 V (0.38%)80.2 W✓ OK (≤3%)
400 mm²570 A445 A0.69 V (0.17%)399.3 V1.15 V (0.29%)60.2 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 50 Ampere ved 150 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 50A over 150 meter (400V)?

Etter NEK 400 anbefales 25 mm² kobberkabel for 50A ved 150 meter (400V), som gir et spenningsfall på 11.12V (2.78%).

Hvor mange kW tåler 50A ved 400V?

Kursen leverer opptil 34.64 kW med 50A vern.