Kabeltverrsnitt for 550 Ampere ved 175 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 550 A over 175 m ved 400V.
Copper Cable (≤3% Drop)400 mm²Drop: 8.92V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.71V (3.68%)
Voltage at Load391.1 VLine Loss: 8496.5 W
Max Power & Breaker381.05 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2378.39 V (594.6%) | 0.0 V | 3923.24 V (980.81%) | 2265725.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1427.04 V (356.76%) | 0.0 V | 2353.94 V (588.49%) | 1359435.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 891.9 V (222.97%) | 0.0 V | 1471.21 V (367.8%) | 849646.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 594.6 V (148.65%) | 0.0 V | 980.81 V (245.2%) | 566431.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 356.76 V (89.19%) | 43.2 V | 588.49 V (147.12%) | 339858.7 W | Drop High |
| 16 mm² | 76 A | 59 A | 222.97 V (55.74%) | 177.0 V | 367.8 V (91.95%) | 212411.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 142.7 V (35.68%) | 257.3 V | 235.39 V (58.85%) | 135943.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 101.93 V (25.48%) | 298.1 V | 168.14 V (42.03%) | 97102.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 71.35 V (17.84%) | 328.6 V | 117.7 V (29.42%) | 67971.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 50.97 V (12.74%) | 349.0 V | 84.07 V (21.02%) | 48551.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 37.55 V (9.39%) | 362.4 V | 61.95 V (15.49%) | 35774.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 29.73 V (7.43%) | 370.3 V | 49.04 V (12.26%) | 28321.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 23.78 V (5.95%) | 376.2 V | 39.23 V (9.81%) | 22657.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 19.28 V (4.82%) | 380.7 V | 31.81 V (7.95%) | 18370.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 14.86 V (3.72%) | 385.1 V | 24.52 V (6.13%) | 14160.8 W | Drop High |
| 300 mm² | 477 A | 372 A | 11.89 V (2.97%) | 388.1 V | 19.62 V (4.9%) | 11328.6 W | Drop High |
| 400 mm² | 570 A | 445 A | 8.92 V (2.23%) | 391.1 V | 14.71 V (3.68%) | 8496.5 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 550 Ampere ved 175 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 550A over 175 meter (400V)?
Etter NEK 400 anbefales 400 mm² kobberkabel for 550A ved 175 meter (400V), som gir et spenningsfall på 8.92V (2.23%).
Hvor mange kW tåler 550A ved 400V?
Kursen leverer opptil 381.05 kW med 600A vern.
Related Lengths & Currents (400V)
550A · 5m (400V)550A · 10m (400V)550A · 15m (400V)550A · 20m (400V)550A · 25m (400V)550A · 30m (400V)550A · 35m (400V)550A · 40m (400V)550A · 45m (400V)550A · 50m (400V)550A · 60m (400V)550A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)