Kabeltverrsnitt for 80 Ampere ved 400 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 80 A over 400 m ved 400V.
Copper Cable (≤3% Drop)120 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.58V (2.64%)
Voltage at Load390.1 VLine Loss: 1369.6 W
Max Power & Breaker55.43 kW80A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 790.74 V (197.68%) | 0.0 V | 1304.35 V (326.09%) | 109568.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 474.44 V (118.61%) | 0.0 V | 782.61 V (195.65%) | 65740.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 296.53 V (74.13%) | 103.5 V | 489.13 V (122.28%) | 41088.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 197.68 V (49.42%) | 202.3 V | 326.09 V (81.52%) | 27392.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 118.61 V (29.65%) | 281.4 V | 195.65 V (48.91%) | 16435.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 74.13 V (18.53%) | 325.9 V | 122.28 V (30.57%) | 10272.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 47.44 V (11.86%) | 352.6 V | 78.26 V (19.57%) | 6574.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 33.89 V (8.47%) | 366.1 V | 55.9 V (13.98%) | 4695.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 23.72 V (5.93%) | 376.3 V | 39.13 V (9.78%) | 3287.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 16.94 V (4.24%) | 383.1 V | 27.95 V (6.99%) | 2347.9 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 12.49 V (3.12%) | 387.5 V | 20.59 V (5.15%) | 1730.0 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 9.88 V (2.47%) | 390.1 V | 16.3 V (4.08%) | 1369.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 7.91 V (1.98%) | 392.1 V | 13.04 V (3.26%) | 1095.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 6.41 V (1.6%) | 393.6 V | 10.58 V (2.64%) | 888.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 4.94 V (1.24%) | 395.1 V | 8.15 V (2.04%) | 684.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.95 V (0.99%) | 396.0 V | 6.52 V (1.63%) | 547.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 410.9 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 80 Ampere ved 400 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 80A over 400 meter (400V)?
Etter NEK 400 anbefales 120 mm² kobberkabel for 80A ved 400 meter (400V), som gir et spenningsfall på 9.88V (2.47%).
Hvor mange kW tåler 80A ved 400V?
Kursen leverer opptil 55.43 kW med 80A vern.
Related Lengths & Currents (400V)
80A · 5m (400V)80A · 10m (400V)80A · 15m (400V)80A · 20m (400V)80A · 25m (400V)80A · 30m (400V)80A · 35m (400V)80A · 40m (400V)80A · 45m (400V)80A · 50m (400V)80A · 60m (400V)80A · 70m (400V)10A · 400m (400V)16A · 400m (400V)20A · 400m (400V)25A · 400m (400V)32A · 400m (400V)40A · 400m (400V)50A · 400m (400V)63A · 400m (400V)100A · 400m (400V)125A · 400m (400V)160A · 400m (400V)200A · 400m (400V)