⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 800 Ampere ved 90 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 800 A over 90 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.85V (1.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.71V (5.53%)
Voltage at Load226.2 VLine Loss: 3081.6 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2054.4 V (893.22%)0.0 V3388.8 V (1473.39%)1643520.0 WDrop High
2.5 mm²24 A18 A1232.64 V (535.93%)0.0 V2033.28 V (884.03%)986112.0 WDrop High
4 mm²32 A25 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)616320.0 WDrop High
6 mm²41 A32 A513.6 V (223.3%)0.0 V847.2 V (368.35%)410880.0 WDrop High
10 mm²57 A44 A308.16 V (133.98%)0.0 V508.32 V (221.01%)246528.0 WDrop High
16 mm²76 A59 A192.6 V (83.74%)37.4 V317.7 V (138.13%)154080.0 WDrop High
25 mm²101 A78 A123.26 V (53.59%)106.7 V203.33 V (88.4%)98611.2 WDrop High
35 mm²125 A97 A88.05 V (38.28%)142.0 V145.23 V (63.15%)70436.6 WDrop High
50 mm²151 A118 A61.63 V (26.8%)168.4 V101.66 V (44.2%)49305.6 WDrop High
70 mm²192 A150 A44.02 V (19.14%)186.0 V72.62 V (31.57%)35218.3 WDrop High
95 mm²232 A181 A32.44 V (14.1%)197.6 V53.51 V (23.26%)25950.3 WDrop High
120 mm²269 A210 A25.68 V (11.17%)204.3 V42.36 V (18.42%)20544.0 WDrop High
150 mm²309 A241 A20.54 V (8.93%)209.5 V33.89 V (14.73%)16435.2 WDrop High
185 mm²353 A275 A16.66 V (7.24%)213.3 V27.48 V (11.95%)13325.8 WDrop High
240 mm²415 A324 A12.84 V (5.58%)217.2 V21.18 V (9.21%)10272.0 WDrop High
300 mm²477 A372 A10.27 V (4.47%)219.7 V16.94 V (7.37%)8217.6 WDrop High
400 mm²570 A445 A7.7 V (3.35%)222.3 V12.71 V (5.53%)6163.2 WDrop High

FAQ — Kabeltverrsnitt for 800 Ampere ved 90 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 800A over 90 meter (230V)?

Etter NEK 400 anbefales 2× 400 mm² kobberkabel for 800A ved 90 meter (230V), som gir et spenningsfall på 3.85V (1.68%).

Hvor mange kW tåler 800A ved 230V?

Kursen leverer opptil 184.0 kW med 800A vern.