Kabelarea för 20 Ampere vid 500 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 20 A över 500 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.11V (2.66%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.88V (2.56%)
Voltage at Load223.9 VLine Loss: 122.3 W
Max Power & Breaker4.6 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A285.33 V (124.06%)0.0 V470.67 V (204.64%)5706.7 WDrop High
2.5 mm²24 A18 A171.2 V (74.43%)58.8 V282.4 V (122.78%)3424.0 WDrop High
4 mm²32 A25 A107.0 V (46.52%)123.0 V176.5 V (76.74%)2140.0 WDrop High
6 mm²41 A32 A71.33 V (31.01%)158.7 V117.67 V (51.16%)1426.7 WDrop High
10 mm²57 A44 A42.8 V (18.61%)187.2 V70.6 V (30.7%)856.0 WDrop High
16 mm²76 A59 A26.75 V (11.63%)203.2 V44.12 V (19.18%)535.0 WDrop High
25 mm²101 A78 A17.12 V (7.44%)212.9 V28.24 V (12.28%)342.4 WDrop High
35 mm²125 A97 A12.23 V (5.32%)217.8 V20.17 V (8.77%)244.6 WDrop High
50 mm²151 A118 A8.56 V (3.72%)221.4 V14.12 V (6.14%)171.2 W~ ≤5%
70 mm²192 A150 A6.11 V (2.66%)223.9 V10.09 V (4.39%)122.3 W✓ OK (≤3%)
95 mm²232 A181 A4.51 V (1.96%)225.5 V7.43 V (3.23%)90.1 W✓ OK (≤3%)
120 mm²269 A210 A3.57 V (1.55%)226.4 V5.88 V (2.56%)71.3 W✓ OK (≤3%)
150 mm²309 A241 A2.85 V (1.24%)227.1 V4.71 V (2.05%)57.1 W✓ OK (≤3%)
185 mm²353 A275 A2.31 V (1.01%)227.7 V3.82 V (1.66%)46.3 W✓ OK (≤3%)
240 mm²415 A324 A1.78 V (0.78%)228.2 V2.94 V (1.28%)35.7 W✓ OK (≤3%)
300 mm²477 A372 A1.43 V (0.62%)228.6 V2.35 V (1.02%)28.5 W✓ OK (≤3%)
400 mm²570 A445 A1.07 V (0.47%)228.9 V1.76 V (0.77%)21.4 W✓ OK (≤3%)

FAQ — Kabelarea för 20 Ampere vid 500 Meter (230V)

Vilken kabelarea krävs för 20A vid 500 meter (230V)?

För 20 Ampere över 500 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (6.11V / 2.66%).

Hur stor effekt motsvarar 20A vid 230V?

Det motsvarar 4.6 kW med en rekommenderad säkring på 20A.