⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 40 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 45 m vid 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 11.01V (2.75%)
Voltage at Load388.9 VLine Loss: 770.4 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A44.48 V (11.12%)355.5 V73.37 V (18.34%)3081.6 WDrop High
2.5 mm²24 A18 A26.69 V (6.67%)373.3 V44.02 V (11.01%)1849.0 WDrop High
4 mm²32 A25 A16.68 V (4.17%)383.3 V27.51 V (6.88%)1155.6 WDrop High
6 mm²41 A32 A11.12 V (2.78%)388.9 V18.34 V (4.59%)770.4 W✓ OK (≤3%)
10 mm²57 A44 A6.67 V (1.67%)393.3 V11.01 V (2.75%)462.2 W✓ OK (≤3%)
16 mm²76 A59 A4.17 V (1.04%)395.8 V6.88 V (1.72%)288.9 W✓ OK (≤3%)
25 mm²101 A78 A2.67 V (0.67%)397.3 V4.4 V (1.1%)184.9 W✓ OK (≤3%)
35 mm²125 A97 A1.91 V (0.48%)398.1 V3.14 V (0.79%)132.1 W✓ OK (≤3%)
50 mm²151 A118 A1.33 V (0.33%)398.7 V2.2 V (0.55%)92.4 W✓ OK (≤3%)
70 mm²192 A150 A0.95 V (0.24%)399.0 V1.57 V (0.39%)66.0 W✓ OK (≤3%)
95 mm²232 A181 A0.7 V (0.18%)399.3 V1.16 V (0.29%)48.7 W✓ OK (≤3%)
120 mm²269 A210 A0.56 V (0.14%)399.4 V0.92 V (0.23%)38.5 W✓ OK (≤3%)
150 mm²309 A241 A0.44 V (0.11%)399.6 V0.73 V (0.18%)30.8 W✓ OK (≤3%)
185 mm²353 A275 A0.36 V (0.09%)399.6 V0.59 V (0.15%)25.0 W✓ OK (≤3%)
240 mm²415 A324 A0.28 V (0.07%)399.7 V0.46 V (0.11%)19.3 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.06%)399.8 V0.37 V (0.09%)15.4 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.04%)399.8 V0.28 V (0.07%)11.6 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 40A vid 45 meter (400V)?

För 40 Ampere över 45 meter vid 400V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 40A vid 400V?

Det motsvarar 27.71 kW med en rekommenderad säkring på 40A.