Kabelarea för 600 Ampere vid 100 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 100 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.21V (1.4%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.59V (4.6%)
Voltage at Load226.8 VLine Loss: 1926.0 W
Max Power & Breaker138.0 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1712.0 V (744.35%) | 0.0 V | 2824.0 V (1227.83%) | 1027200.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1027.2 V (446.61%) | 0.0 V | 1694.4 V (736.7%) | 616320.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 642.0 V (279.13%) | 0.0 V | 1059.0 V (460.43%) | 385200.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 428.0 V (186.09%) | 0.0 V | 706.0 V (306.96%) | 256800.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 256.8 V (111.65%) | 0.0 V | 423.6 V (184.17%) | 154080.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 160.5 V (69.78%) | 69.5 V | 264.75 V (115.11%) | 96300.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 102.72 V (44.66%) | 127.3 V | 169.44 V (73.67%) | 61632.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 73.37 V (31.9%) | 156.6 V | 121.03 V (52.62%) | 44022.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 51.36 V (22.33%) | 178.6 V | 84.72 V (36.83%) | 30816.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 36.69 V (15.95%) | 193.3 V | 60.51 V (26.31%) | 22011.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 27.03 V (11.75%) | 203.0 V | 44.59 V (19.39%) | 16218.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 21.4 V (9.3%) | 208.6 V | 35.3 V (15.35%) | 12840.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 17.12 V (7.44%) | 212.9 V | 28.24 V (12.28%) | 10272.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 13.88 V (6.04%) | 216.1 V | 22.9 V (9.96%) | 8328.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 10.7 V (4.65%) | 219.3 V | 17.65 V (7.67%) | 6420.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 5136.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 6.42 V (2.79%) | 223.6 V | 10.59 V (4.6%) | 3852.0 W | Drop High |
FAQ — Kabelarea för 600 Ampere vid 100 Meter (230V)
Vilken kabelarea krävs för 600A vid 100 meter (230V)?
För 600 Ampere över 100 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.21V / 1.4%).
Hur stor effekt motsvarar 600A vid 230V?
Det motsvarar 138.0 kW med en rekommenderad säkring på 600A.
Related Lengths & Currents (230V)
600A · 5m (230V)600A · 10m (230V)600A · 15m (230V)600A · 20m (230V)600A · 25m (230V)600A · 30m (230V)600A · 35m (230V)600A · 40m (230V)600A · 45m (230V)600A · 50m (230V)600A · 60m (230V)600A · 70m (230V)10A · 100m (230V)16A · 100m (230V)20A · 100m (230V)25A · 100m (230V)32A · 100m (230V)40A · 100m (230V)50A · 100m (230V)63A · 100m (230V)80A · 100m (230V)100A · 100m (230V)125A · 100m (230V)160A · 100m (230V)200A · 100m (230V)