Kabelarea för 600 Ampere vid 100 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 100 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.21V (1.4%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.59V (4.6%)
Voltage at Load226.8 VLine Loss: 1926.0 W
Max Power & Breaker138.0 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1712.0 V (744.35%)0.0 V2824.0 V (1227.83%)1027200.0 WDrop High
2.5 mm²24 A18 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)616320.0 WDrop High
4 mm²32 A25 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)385200.0 WDrop High
6 mm²41 A32 A428.0 V (186.09%)0.0 V706.0 V (306.96%)256800.0 WDrop High
10 mm²57 A44 A256.8 V (111.65%)0.0 V423.6 V (184.17%)154080.0 WDrop High
16 mm²76 A59 A160.5 V (69.78%)69.5 V264.75 V (115.11%)96300.0 WDrop High
25 mm²101 A78 A102.72 V (44.66%)127.3 V169.44 V (73.67%)61632.0 WDrop High
35 mm²125 A97 A73.37 V (31.9%)156.6 V121.03 V (52.62%)44022.9 WDrop High
50 mm²151 A118 A51.36 V (22.33%)178.6 V84.72 V (36.83%)30816.0 WDrop High
70 mm²192 A150 A36.69 V (15.95%)193.3 V60.51 V (26.31%)22011.4 WDrop High
95 mm²232 A181 A27.03 V (11.75%)203.0 V44.59 V (19.39%)16218.9 WDrop High
120 mm²269 A210 A21.4 V (9.3%)208.6 V35.3 V (15.35%)12840.0 WDrop High
150 mm²309 A241 A17.12 V (7.44%)212.9 V28.24 V (12.28%)10272.0 WDrop High
185 mm²353 A275 A13.88 V (6.04%)216.1 V22.9 V (9.96%)8328.6 WDrop High
240 mm²415 A324 A10.7 V (4.65%)219.3 V17.65 V (7.67%)6420.0 WDrop High
300 mm²477 A372 A8.56 V (3.72%)221.4 V14.12 V (6.14%)5136.0 WDrop High
400 mm²570 A445 A6.42 V (2.79%)223.6 V10.59 V (4.6%)3852.0 WDrop High

FAQ — Kabelarea för 600 Ampere vid 100 Meter (230V)

Vilken kabelarea krävs för 600A vid 100 meter (230V)?

För 600 Ampere över 100 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.21V / 1.4%).

Hur stor effekt motsvarar 600A vid 230V?

Det motsvarar 138.0 kW med en rekommenderad säkring på 600A.