🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.36%
Aluminum Wire (≤3% Drop)14 AWGDrop: 5.38V (2.24%)
Voltage at Load End236.7 VLoss: 3.26 V (56.4 W)
Power & Breaker (125%)4.16 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3.26 V (1.36%)236.7 V5.38 V (2.24%)56.4 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A2.05 V (0.85%)238.0 V3.38 V (1.41%)35.5 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A1.29 V (0.54%)238.7 V2.13 V (0.89%)22.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A0.81 V (0.34%)239.2 V1.34 V (0.56%)14.0 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.51 V (0.21%)239.5 V0.84 V (0.35%)8.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.32 V (0.13%)239.7 V0.53 V (0.22%)5.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.25 V (0.11%)239.7 V0.42 V (0.17%)4.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.2 V (0.08%)239.8 V0.33 V (0.14%)3.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.16 V (0.07%)239.8 V0.26 V (0.11%)2.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.13 V (0.05%)239.9 V0.21 V (0.09%)2.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.1 V (0.04%)239.9 V0.17 V (0.07%)1.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.08 V (0.03%)239.9 V0.13 V (0.05%)1.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.06 V (0.03%)239.9 V0.1 V (0.04%)1.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.05 V (0.02%)239.9 V0.09 V (0.04%)0.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.04 V (0.02%)240.0 V0.07 V (0.03%)0.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.04 V (0.02%)240.0 V0.06 V (0.03%)0.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.03 V (0.01%)240.0 V0.06 V (0.02%)0.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.03 V (0.01%)240.0 V0.04 V (0.02%)0.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.02 V (0.01%)240.0 V0.04 V (0.02%)0.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.01%)240.0 V0.03 V (0.01%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.01%)240.0 V0.02 V (0.01%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 60 feet one-way at 240V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 3.26V (1.36%) and delivers 236.7V at the load.

What size aluminum wire is required for 10 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 5.38V (2.24%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.