🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 75 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.76V (1.33%)
Voltage at Load End207.2 VLoss: 0.83 V (1448.2 W)
Power & Breaker (125%)360.27 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 75 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A407.37 V (195.85%)0.0 V671.97 V (323.06%)705582.7 WDrop/Amp High
12 AWG3.31 mm²20 A255.99 V (123.07%)0.0 V422.26 V (203.01%)443387.3 WDrop/Amp High
10 AWG5.26 mm²30 A161.09 V (77.45%)46.9 V265.72 V (127.75%)279013.7 WDrop/Amp High
8 AWG8.37 mm²50 A101.23 V (48.67%)106.8 V166.99 V (80.28%)175341.9 WDrop/Amp High
6 AWG13.3 mm²65 A63.71 V (30.63%)144.3 V105.09 V (50.52%)110346.8 WDrop/Amp High
4 AWG21.15 mm²85 A40.06 V (19.26%)167.9 V66.08 V (31.77%)69390.6 WDrop/Amp High
3 AWG26.67 mm²100 A31.77 V (15.27%)176.2 V52.41 V (25.2%)55028.6 WDrop/Amp High
2 AWG33.62 mm²115 A25.2 V (12.12%)182.8 V41.57 V (19.99%)43652.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.98 V (9.61%)188.0 V32.96 V (15.84%)34605.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.84 V (7.62%)192.2 V26.13 V (12.56%)27437.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.57 V (6.04%)195.4 V20.73 V (9.97%)21765.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.97 V (4.79%)198.0 V16.44 V (7.9%)17264.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.9 V (3.8%)200.1 V13.04 V (6.27%)13690.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.69 V (3.22%)201.3 V11.03 V (5.3%)11583.4 WDrop/Amp High
300 kcmil152.0 mm²285 A5.57 V (2.68%)202.4 V9.2 V (4.42%)9655.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.78 V (2.3%)203.2 V7.88 V (3.79%)8277.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.18 V (2.01%)203.8 V6.9 V (3.32%)7240.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.34 V (1.61%)204.7 V5.52 V (2.65%)5791.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.79 V (1.34%)205.2 V4.6 V (2.21%)4827.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.23 V (1.07%)205.8 V3.68 V (1.77%)3862.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.67 V (0.8%)206.3 V2.76 V (1.33%)2896.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 75 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 75 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.83V (0.4%) and delivers 207.2V at the load.

What size aluminum wire is required for 1000 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.76V (1.33%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.