⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)4 AWGDrop: 6.87V (2.86%)
Voltage at Load End233.4 VLoss: 6.62 V (297.9 W)
Power & Breaker (125%)10.8 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A42.33 V (17.64%)197.7 V69.83 V (29.1%)1905.1 WDrop/Amp High
12 AWG3.31 mm²20 A26.6 V (11.08%)213.4 V43.88 V (18.28%)1197.1 WDrop/Amp High
10 AWG5.26 mm²30 A16.74 V (6.98%)223.3 V27.61 V (11.51%)753.3 WDrop/Amp High
8 AWG8.37 mm²50 A10.52 V (4.38%)229.5 V17.35 V (7.23%)473.4 W~ ≤5%
6 AWG13.3 mm²65 A6.62 V (2.76%)233.4 V10.92 V (4.55%)297.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.16 V (1.73%)235.8 V6.87 V (2.86%)187.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.3 V (1.38%)236.7 V5.45 V (2.27%)148.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.62 V (1.09%)237.4 V4.32 V (1.8%)117.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.08 V (0.87%)237.9 V3.42 V (1.43%)93.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.65 V (0.69%)238.4 V2.72 V (1.13%)74.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.31 V (0.54%)238.7 V2.15 V (0.9%)58.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.04 V (0.43%)239.0 V1.71 V (0.71%)46.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.82 V (0.34%)239.2 V1.35 V (0.56%)37.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.7 V (0.29%)239.3 V1.15 V (0.48%)31.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.58 V (0.24%)239.4 V0.96 V (0.4%)26.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.5 V (0.21%)239.5 V0.82 V (0.34%)22.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.43 V (0.18%)239.6 V0.72 V (0.3%)19.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.35 V (0.14%)239.7 V0.57 V (0.24%)15.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.29 V (0.12%)239.7 V0.48 V (0.2%)13.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.23 V (0.1%)239.8 V0.38 V (0.16%)10.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.07%)239.8 V0.29 V (0.12%)7.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 150 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 6.62V (2.76%) and delivers 233.4V at the load.

What size aluminum wire is required for 45 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 6.87V (2.86%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.