⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.87V (1.19%)
Voltage at Load End237.7 VLoss: 2.32 V (1042.8 W)
Power & Breaker (125%)108.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A423.35 V (176.4%)0.0 V698.33 V (290.97%)190507.3 WDrop/Amp High
12 AWG3.31 mm²20 A266.03 V (110.85%)0.0 V438.83 V (182.85%)119714.6 WDrop/Amp High
10 AWG5.26 mm²30 A167.41 V (69.75%)72.6 V276.15 V (115.06%)75333.7 WDrop/Amp High
8 AWG8.37 mm²50 A105.21 V (43.84%)134.8 V173.54 V (72.31%)47342.3 WDrop/Amp High
6 AWG13.3 mm²65 A66.21 V (27.59%)173.8 V109.21 V (45.51%)29793.6 WDrop/Amp High
4 AWG21.15 mm²85 A41.63 V (17.35%)198.4 V68.68 V (28.62%)18735.5 WDrop/Amp High
3 AWG26.67 mm²100 A33.02 V (13.76%)207.0 V54.46 V (22.69%)14857.7 WDrop/Amp High
2 AWG33.62 mm²115 A26.19 V (10.91%)213.8 V43.2 V (18.0%)11786.3 WDrop/Amp High
1 AWG42.41 mm²130 A20.76 V (8.65%)219.2 V34.25 V (14.27%)9343.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.46 V (6.86%)223.5 V27.16 V (11.31%)7408.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.06 V (5.44%)226.9 V21.54 V (8.98%)5876.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.36 V (4.32%)229.6 V17.09 V (7.12%)4661.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.21 V (3.42%)231.8 V13.55 V (5.65%)3696.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.95 V (2.9%)233.0 V11.46 V (4.78%)3127.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.79 V (2.41%)234.2 V9.56 V (3.98%)2606.9 WDrop/Amp High
350 kcmil177.3 mm²310 A4.97 V (2.07%)235.0 V8.19 V (3.41%)2234.9 WDrop/Amp High
400 kcmil202.7 mm²335 A4.34 V (1.81%)235.7 V7.17 V (2.99%)1954.9 WDrop/Amp High
500 kcmil253.4 mm²380 A3.48 V (1.45%)236.5 V5.73 V (2.39%)1563.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1303.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.32 V (0.97%)237.7 V3.82 V (1.59%)1042.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.74 V (0.72%)238.3 V2.87 V (1.19%)782.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 150 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.32V (0.97%) and delivers 237.7V at the load.

What size aluminum wire is required for 450 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.87V (1.19%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.