⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.89%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.24V (3.0%)
Voltage at Load End202.0 VLoss: 6.01 V (520.4 W)
Power & Breaker (125%)18.01 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A61.11 V (29.38%)146.9 V100.8 V (48.46%)5291.9 WDrop/Amp High
12 AWG3.31 mm²20 A38.4 V (18.46%)169.6 V63.34 V (30.45%)3325.4 WDrop/Amp High
10 AWG5.26 mm²30 A24.16 V (11.62%)183.8 V39.86 V (19.16%)2092.6 WDrop/Amp High
8 AWG8.37 mm²50 A15.19 V (7.3%)192.8 V25.05 V (12.04%)1315.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.56 V (4.59%)198.4 V15.76 V (7.58%)827.6 W~ ≤5%
4 AWG21.15 mm²85 A6.01 V (2.89%)202.0 V9.91 V (4.77%)520.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.77 V (2.29%)203.2 V7.86 V (3.78%)412.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.78 V (1.82%)204.2 V6.24 V (3.0%)327.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.0 V (1.44%)205.0 V4.94 V (2.38%)259.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.38 V (1.14%)205.6 V3.92 V (1.88%)205.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.88 V (0.91%)206.1 V3.11 V (1.49%)163.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.5 V (0.72%)206.5 V2.47 V (1.19%)129.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.19 V (0.57%)206.8 V1.96 V (0.94%)102.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.0 V (0.48%)207.0 V1.65 V (0.8%)86.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.84 V (0.4%)207.2 V1.38 V (0.66%)72.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.72 V (0.34%)207.3 V1.18 V (0.57%)62.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.63 V (0.3%)207.4 V1.03 V (0.5%)54.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.5 V (0.24%)207.5 V0.83 V (0.4%)43.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.42 V (0.2%)207.6 V0.69 V (0.33%)36.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.16%)207.7 V0.55 V (0.27%)29.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.12%)207.7 V0.41 V (0.2%)21.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 225 feet one-way at 208V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 6.01V (2.89%) and delivers 202.0V at the load.

What size aluminum wire is required for 50 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.24V (3.0%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.