🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.69V (9.95%)
Voltage at Load End203.8 VLoss: 4.18 V (5430.8 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3055.26 V (1468.88%)0.0 V5039.76 V (2422.96%)3968902.6 WDrop/Amp High
12 AWG3.31 mm²20 A1919.92 V (923.04%)0.0 V3166.98 V (1522.58%)2494053.6 WDrop/Amp High
10 AWG5.26 mm²30 A1208.16 V (580.85%)0.0 V1992.91 V (958.13%)1569452.0 WDrop/Amp High
8 AWG8.37 mm²50 A759.25 V (365.03%)0.0 V1252.41 V (602.12%)986298.4 WDrop/Amp High
6 AWG13.3 mm²65 A477.82 V (229.72%)0.0 V788.17 V (378.93%)620700.6 WDrop/Amp High
4 AWG21.15 mm²85 A300.47 V (144.46%)0.0 V495.64 V (238.29%)390322.3 WDrop/Amp High
3 AWG26.67 mm²100 A238.28 V (114.56%)0.0 V393.05 V (188.97%)309535.7 WDrop/Amp High
2 AWG33.62 mm²115 A189.02 V (90.88%)19.0 V311.8 V (149.9%)245547.8 WDrop/Amp High
1 AWG42.41 mm²130 A149.85 V (72.04%)58.2 V247.18 V (118.83%)194655.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.81 V (57.12%)89.2 V195.97 V (94.22%)154333.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A94.25 V (45.31%)113.8 V155.46 V (74.74%)122428.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.76 V (35.94%)133.2 V123.31 V (59.28%)97110.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.28 V (28.5%)148.7 V97.79 V (47.01%)77008.6 WDrop/Amp High
250 kcmil126.7 mm²255 A50.16 V (24.11%)157.8 V82.74 V (39.78%)65156.4 WDrop/Amp High
300 kcmil152.0 mm²285 A41.81 V (20.1%)166.2 V68.97 V (33.16%)54311.3 WDrop/Amp High
350 kcmil177.3 mm²310 A35.84 V (17.23%)172.2 V59.12 V (28.43%)46561.3 WDrop/Amp High
400 kcmil202.7 mm²335 A31.35 V (15.07%)176.6 V51.72 V (24.86%)40726.8 WDrop/Amp High
500 kcmil253.4 mm²380 A25.08 V (12.06%)182.9 V41.37 V (19.89%)32578.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.9 V (10.05%)187.1 V34.48 V (16.58%)27155.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.72 V (8.04%)191.3 V27.59 V (13.26%)21724.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.54 V (6.03%)195.5 V20.69 V (9.95%)16292.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 750 feet one-way at 208V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.18V (2.01%) and delivers 203.8V at the load.

What size aluminum wire is required for 750 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.69V (9.95%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.