100 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 6.76V (2.94%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 5.72V (2.49%)
Voltage at Load223.2 VLine Loss: 675.8 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A428.0 V (186.09%)0.0 V706.0 V (306.96%)42800.0 WDrop High
2.5 mm²24 A18 A256.8 V (111.65%)0.0 V423.6 V (184.17%)25680.0 WDrop High
4 mm²32 A25 A160.5 V (69.78%)69.5 V264.75 V (115.11%)16050.0 WDrop High
6 mm²41 A32 A107.0 V (46.52%)123.0 V176.5 V (76.74%)10700.0 WDrop High
10 mm²57 A44 A64.2 V (27.91%)165.8 V105.9 V (46.04%)6420.0 WDrop High
16 mm²76 A59 A40.12 V (17.45%)189.9 V66.19 V (28.78%)4012.5 WDrop High
25 mm²101 A78 A25.68 V (11.17%)204.3 V42.36 V (18.42%)2568.0 WDrop High
35 mm²125 A97 A18.34 V (7.98%)211.7 V30.26 V (13.16%)1834.3 WDrop High
50 mm²151 A118 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1284.0 WDrop High
70 mm²192 A150 A9.17 V (3.99%)220.8 V15.13 V (6.58%)917.1 W~ ≤5%
95 mm²232 A181 A6.76 V (2.94%)223.2 V11.15 V (4.85%)675.8 W✓ OK (≤3%)
120 mm²269 A210 A5.35 V (2.33%)224.7 V8.82 V (3.84%)535.0 W✓ OK (≤3%)
150 mm²309 A241 A4.28 V (1.86%)225.7 V7.06 V (3.07%)428.0 W✓ OK (≤3%)
185 mm²353 A275 A3.47 V (1.51%)226.5 V5.72 V (2.49%)347.0 W✓ OK (≤3%)
240 mm²415 A324 A2.67 V (1.16%)227.3 V4.41 V (1.92%)267.5 W✓ OK (≤3%)
300 mm²477 A372 A2.14 V (0.93%)227.9 V3.53 V (1.53%)214.0 W✓ OK (≤3%)
400 mm²570 A445 A1.6 V (0.7%)228.4 V2.65 V (1.15%)160.5 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 100A at 150 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 100A over 150m at 230V (voltage drop: 6.76V or 2.94%).

What is the power capacity of 100A at 230V?

At unity power factor, 100A at 230V supports 23.0 kW with a standard 100A circuit breaker.