40 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.05V (2.63%)
Voltage at Load224.9 VLine Loss: 205.4 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A171.2 V (74.43%)58.8 V282.4 V (122.78%)6848.0 WDrop High
2.5 mm²24 A18 A102.72 V (44.66%)127.3 V169.44 V (73.67%)4108.8 WDrop High
4 mm²32 A25 A64.2 V (27.91%)165.8 V105.9 V (46.04%)2568.0 WDrop High
6 mm²41 A32 A42.8 V (18.61%)187.2 V70.6 V (30.7%)1712.0 WDrop High
10 mm²57 A44 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1027.2 WDrop High
16 mm²76 A59 A16.05 V (6.98%)213.9 V26.48 V (11.51%)642.0 WDrop High
25 mm²101 A78 A10.27 V (4.47%)219.7 V16.94 V (7.37%)410.9 W~ ≤5%
35 mm²125 A97 A7.34 V (3.19%)222.7 V12.1 V (5.26%)293.5 W~ ≤5%
50 mm²151 A118 A5.14 V (2.23%)224.9 V8.47 V (3.68%)205.4 W✓ OK (≤3%)
70 mm²192 A150 A3.67 V (1.6%)226.3 V6.05 V (2.63%)146.7 W✓ OK (≤3%)
95 mm²232 A181 A2.7 V (1.18%)227.3 V4.46 V (1.94%)108.1 W✓ OK (≤3%)
120 mm²269 A210 A2.14 V (0.93%)227.9 V3.53 V (1.53%)85.6 W✓ OK (≤3%)
150 mm²309 A241 A1.71 V (0.74%)228.3 V2.82 V (1.23%)68.5 W✓ OK (≤3%)
185 mm²353 A275 A1.39 V (0.6%)228.6 V2.29 V (1.0%)55.5 W✓ OK (≤3%)
240 mm²415 A324 A1.07 V (0.47%)228.9 V1.76 V (0.77%)42.8 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (0.37%)229.1 V1.41 V (0.61%)34.2 W✓ OK (≤3%)
400 mm²570 A445 A0.64 V (0.28%)229.4 V1.06 V (0.46%)25.7 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 40A at 150 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 40A over 150m at 230V (voltage drop: 5.14V or 2.23%).

What is the power capacity of 40A at 230V?

At unity power factor, 40A at 230V supports 9.2 kW with a standard 40A circuit breaker.