100 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 10.59V (2.55%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 10.19V (2.46%)
Voltage at Load404.4 VLine Loss: 1834.3 W
Max Power & Breaker71.88 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A494.21 V (119.09%)0.0 V815.22 V (196.44%)85600.0 WDrop High
2.5 mm²24 A18 A296.53 V (71.45%)118.5 V489.13 V (117.86%)51360.0 WDrop High
4 mm²32 A25 A185.33 V (44.66%)229.7 V305.71 V (73.66%)32100.0 WDrop High
6 mm²41 A32 A123.55 V (29.77%)291.4 V203.8 V (49.11%)21400.0 WDrop High
10 mm²57 A44 A74.13 V (17.86%)340.9 V122.28 V (29.47%)12840.0 WDrop High
16 mm²76 A59 A46.33 V (11.16%)368.7 V76.43 V (18.42%)8025.0 WDrop High
25 mm²101 A78 A29.65 V (7.15%)385.3 V48.91 V (11.79%)5136.0 WDrop High
35 mm²125 A97 A21.18 V (5.1%)393.8 V34.94 V (8.42%)3668.6 WDrop High
50 mm²151 A118 A14.83 V (3.57%)400.2 V24.46 V (5.89%)2568.0 W~ ≤5%
70 mm²192 A150 A10.59 V (2.55%)404.4 V17.47 V (4.21%)1834.3 W✓ OK (≤3%)
95 mm²232 A181 A7.8 V (1.88%)407.2 V12.87 V (3.1%)1351.6 W✓ OK (≤3%)
120 mm²269 A210 A6.18 V (1.49%)408.8 V10.19 V (2.46%)1070.0 W✓ OK (≤3%)
150 mm²309 A241 A4.94 V (1.19%)410.1 V8.15 V (1.96%)856.0 W✓ OK (≤3%)
185 mm²353 A275 A4.01 V (0.97%)411.0 V6.61 V (1.59%)694.1 W✓ OK (≤3%)
240 mm²415 A324 A3.09 V (0.74%)411.9 V5.1 V (1.23%)535.0 W✓ OK (≤3%)
300 mm²477 A372 A2.47 V (0.6%)412.5 V4.08 V (0.98%)428.0 W✓ OK (≤3%)
400 mm²570 A445 A1.85 V (0.45%)413.1 V3.06 V (0.74%)321.0 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 100A at 200 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 100A over 200m at 415V (voltage drop: 10.59V or 2.55%).

What is the power capacity of 100A at 415V?

At unity power factor, 100A at 415V supports 71.88 kW with a standard 100A circuit breaker.