100 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 2.97V (0.71%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 2.45V (0.59%)
Voltage at Load412.0 VLine Loss: 513.6 W
Max Power & Breaker71.88 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (11.91%)365.6 V81.52 V (19.64%)8560.0 WDrop High
2.5 mm²24 A18 A29.65 V (7.15%)385.3 V48.91 V (11.79%)5136.0 WDrop High
4 mm²32 A25 A18.53 V (4.47%)396.5 V30.57 V (7.37%)3210.0 WDrop High
6 mm²41 A32 A12.36 V (2.98%)402.6 V20.38 V (4.91%)2140.0 WDrop High
10 mm²57 A44 A7.41 V (1.79%)407.6 V12.23 V (2.95%)1284.0 WDrop High
16 mm²76 A59 A4.63 V (1.12%)410.4 V7.64 V (1.84%)802.5 WDrop High
25 mm²101 A78 A2.97 V (0.71%)412.0 V4.89 V (1.18%)513.6 W✓ OK (≤3%)
35 mm²125 A97 A2.12 V (0.51%)412.9 V3.49 V (0.84%)366.9 W✓ OK (≤3%)
50 mm²151 A118 A1.48 V (0.36%)413.5 V2.45 V (0.59%)256.8 W✓ OK (≤3%)
70 mm²192 A150 A1.06 V (0.26%)413.9 V1.75 V (0.42%)183.4 W✓ OK (≤3%)
95 mm²232 A181 A0.78 V (0.19%)414.2 V1.29 V (0.31%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (0.15%)414.4 V1.02 V (0.25%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A0.49 V (0.12%)414.5 V0.82 V (0.2%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.1%)414.6 V0.66 V (0.16%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.07%)414.7 V0.51 V (0.12%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.06%)414.8 V0.41 V (0.1%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.04%)414.8 V0.31 V (0.07%)32.1 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 100A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 100A over 20m at 415V (voltage drop: 2.97V or 0.71%).

What is the power capacity of 100A at 415V?

At unity power factor, 100A at 415V supports 71.88 kW with a standard 100A circuit breaker.