100 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.95V (2.58%)
Voltage at Load223.2 VLine Loss: 684.8 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A228.27 V (99.25%)1.7 V376.53 V (163.71%)22826.7 WDrop High
2.5 mm²24 A18 A136.96 V (59.55%)93.0 V225.92 V (98.23%)13696.0 WDrop High
4 mm²32 A25 A85.6 V (37.22%)144.4 V141.2 V (61.39%)8560.0 WDrop High
6 mm²41 A32 A57.07 V (24.81%)172.9 V94.13 V (40.93%)5706.7 WDrop High
10 mm²57 A44 A34.24 V (14.89%)195.8 V56.48 V (24.56%)3424.0 WDrop High
16 mm²76 A59 A21.4 V (9.3%)208.6 V35.3 V (15.35%)2140.0 WDrop High
25 mm²101 A78 A13.7 V (5.95%)216.3 V22.59 V (9.82%)1369.6 WDrop High
35 mm²125 A97 A9.78 V (4.25%)220.2 V16.14 V (7.02%)978.3 W~ ≤5%
50 mm²151 A118 A6.85 V (2.98%)223.2 V11.3 V (4.91%)684.8 W✓ OK (≤3%)
70 mm²192 A150 A4.89 V (2.13%)225.1 V8.07 V (3.51%)489.1 W✓ OK (≤3%)
95 mm²232 A181 A3.6 V (1.57%)226.4 V5.95 V (2.58%)360.4 W✓ OK (≤3%)
120 mm²269 A210 A2.85 V (1.24%)227.1 V4.71 V (2.05%)285.3 W✓ OK (≤3%)
150 mm²309 A241 A2.28 V (0.99%)227.7 V3.77 V (1.64%)228.3 W✓ OK (≤3%)
185 mm²353 A275 A1.85 V (0.8%)228.1 V3.05 V (1.33%)185.1 W✓ OK (≤3%)
240 mm²415 A324 A1.43 V (0.62%)228.6 V2.35 V (1.02%)142.7 W✓ OK (≤3%)
300 mm²477 A372 A1.14 V (0.5%)228.9 V1.88 V (0.82%)114.1 W✓ OK (≤3%)
400 mm²570 A445 A0.86 V (0.37%)229.1 V1.41 V (0.61%)85.6 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 100A at 80 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 100A over 80m at 230V (voltage drop: 6.85V or 2.98%).

What is the power capacity of 100A at 230V?

At unity power factor, 100A at 230V supports 23.0 kW with a standard 100A circuit breaker.