40 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 6.45V (2.81%)
Voltage at Load224.5 VLine Loss: 219.1 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A91.31 V (39.7%)138.7 V150.61 V (65.48%)3652.3 WDrop High
2.5 mm²24 A18 A54.78 V (23.82%)175.2 V90.37 V (39.29%)2191.4 WDrop High
4 mm²32 A25 A34.24 V (14.89%)195.8 V56.48 V (24.56%)1369.6 WDrop High
6 mm²41 A32 A22.83 V (9.92%)207.2 V37.65 V (16.37%)913.1 WDrop High
10 mm²57 A44 A13.7 V (5.95%)216.3 V22.59 V (9.82%)547.8 WDrop High
16 mm²76 A59 A8.56 V (3.72%)221.4 V14.12 V (6.14%)342.4 W~ ≤5%
25 mm²101 A78 A5.48 V (2.38%)224.5 V9.04 V (3.93%)219.1 W✓ OK (≤3%)
35 mm²125 A97 A3.91 V (1.7%)226.1 V6.45 V (2.81%)156.5 W✓ OK (≤3%)
50 mm²151 A118 A2.74 V (1.19%)227.3 V4.52 V (1.96%)109.6 W✓ OK (≤3%)
70 mm²192 A150 A1.96 V (0.85%)228.0 V3.23 V (1.4%)78.3 W✓ OK (≤3%)
95 mm²232 A181 A1.44 V (0.63%)228.6 V2.38 V (1.03%)57.7 W✓ OK (≤3%)
120 mm²269 A210 A1.14 V (0.5%)228.9 V1.88 V (0.82%)45.7 W✓ OK (≤3%)
150 mm²309 A241 A0.91 V (0.4%)229.1 V1.51 V (0.65%)36.5 W✓ OK (≤3%)
185 mm²353 A275 A0.74 V (0.32%)229.3 V1.22 V (0.53%)29.6 W✓ OK (≤3%)
240 mm²415 A324 A0.57 V (0.25%)229.4 V0.94 V (0.41%)22.8 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.2%)229.5 V0.75 V (0.33%)18.3 W✓ OK (≤3%)
400 mm²570 A445 A0.34 V (0.15%)229.7 V0.56 V (0.25%)13.7 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 40A at 80 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 40A over 80m at 230V (voltage drop: 5.48V or 2.38%).

What is the power capacity of 40A at 230V?

At unity power factor, 40A at 230V supports 9.2 kW with a standard 40A circuit breaker.