1000 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 91.71V (22.93%)
Voltage at Load388.9 VLine Loss: 19260.0 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14826.35 V (3706.59%)0.0 V24456.56 V (6114.14%)25680000.0 WDrop High
2.5 mm²24 A18 A8895.81 V (2223.95%)0.0 V14673.93 V (3668.48%)15408000.0 WDrop High
4 mm²32 A25 A5559.88 V (1389.97%)0.0 V9171.21 V (2292.8%)9630000.0 WDrop High
6 mm²41 A32 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)6420000.0 WDrop High
10 mm²57 A44 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)3852000.0 WDrop High
16 mm²76 A59 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)2407500.0 WDrop High
25 mm²101 A78 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)1540800.0 WDrop High
35 mm²125 A97 A635.42 V (158.85%)0.0 V1048.14 V (262.03%)1100571.4 WDrop High
50 mm²151 A118 A444.79 V (111.2%)0.0 V733.7 V (183.42%)770400.0 WDrop High
70 mm²192 A150 A317.71 V (79.43%)82.3 V524.07 V (131.02%)550285.7 WDrop High
95 mm²232 A181 A234.1 V (58.53%)165.9 V386.16 V (96.54%)405473.7 WDrop High
120 mm²269 A210 A185.33 V (46.33%)214.7 V305.71 V (76.43%)321000.0 WDrop High
150 mm²309 A241 A148.26 V (37.07%)251.7 V244.57 V (61.14%)256800.0 WDrop High
185 mm²353 A275 A120.21 V (30.05%)279.8 V198.3 V (49.57%)208216.2 WDrop High
240 mm²415 A324 A92.66 V (23.17%)307.3 V152.85 V (38.21%)160500.0 WDrop High
300 mm²477 A372 A74.13 V (18.53%)325.9 V122.28 V (30.57%)128400.0 WDrop High
400 mm²570 A445 A55.6 V (13.9%)344.4 V91.71 V (22.93%)96300.0 WDrop High

FAQ — 1000 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 1000A at 600 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 1000A over 600m at 400V (voltage drop: 11.12V or 2.78%).

What is the power capacity of 1000A at 400V?

At unity power factor, 1000A at 400V supports 692.82 kW with a standard 1000A circuit breaker.