110 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 1.35V (2.8%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.29V (2.7%)
Voltage at Load46.7 VLine Loss: 148.0 W
Max Power & Breaker5.28 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A62.77 V (130.78%)0.0 V103.55 V (215.72%)6905.1 WDrop High
2.5 mm²24 A18 A37.66 V (78.47%)10.3 V62.13 V (129.43%)4143.0 WDrop High
4 mm²32 A25 A23.54 V (49.04%)24.5 V38.83 V (80.9%)2589.4 WDrop High
6 mm²41 A32 A15.69 V (32.69%)32.3 V25.89 V (53.93%)1726.3 WDrop High
10 mm²57 A44 A9.42 V (19.62%)38.6 V15.53 V (32.36%)1035.8 WDrop High
16 mm²76 A59 A5.88 V (12.26%)42.1 V9.71 V (20.22%)647.4 WDrop High
25 mm²101 A78 A3.77 V (7.85%)44.2 V6.21 V (12.94%)414.3 WDrop High
35 mm²125 A97 A2.69 V (5.6%)45.3 V4.44 V (9.25%)295.9 WDrop High
50 mm²151 A118 A1.88 V (3.92%)46.1 V3.11 V (6.47%)207.2 W~ ≤5%
70 mm²192 A150 A1.35 V (2.8%)46.7 V2.22 V (4.62%)148.0 W✓ OK (≤3%)
95 mm²232 A181 A0.99 V (2.06%)47.0 V1.63 V (3.41%)109.0 W✓ OK (≤3%)
120 mm²269 A210 A0.78 V (1.63%)47.2 V1.29 V (2.7%)86.3 W✓ OK (≤3%)
150 mm²309 A241 A0.63 V (1.31%)47.4 V1.04 V (2.16%)69.1 W✓ OK (≤3%)
185 mm²353 A275 A0.51 V (1.06%)47.5 V0.84 V (1.75%)56.0 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.82%)47.6 V0.65 V (1.35%)43.2 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.65%)47.7 V0.52 V (1.08%)34.5 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.49%)47.8 V0.39 V (0.81%)25.9 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 110A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 110A over 20m at 48V (voltage drop: 1.35V or 2.8%).

What is the power capacity of 110A at 48V?

At unity power factor, 110A at 48V supports 5.28 kW with a standard 110A circuit breaker.