15 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 0.55V (2.29%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.64V (2.65%)
Voltage at Load23.4 VLine Loss: 8.3 W
Max Power & Breaker0.36 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.84 V (53.5%)11.2 V21.18 V (88.25%)192.6 WDrop High
2.5 mm²24 A18 A7.7 V (32.1%)16.3 V12.71 V (52.95%)115.6 WDrop High
4 mm²32 A25 A4.82 V (20.06%)19.2 V7.94 V (33.09%)72.2 WDrop High
6 mm²41 A32 A3.21 V (13.38%)20.8 V5.29 V (22.06%)48.1 WDrop High
10 mm²57 A44 A1.93 V (8.03%)22.1 V3.18 V (13.24%)28.9 WDrop High
16 mm²76 A59 A1.2 V (5.02%)22.8 V1.99 V (8.27%)18.1 WDrop High
25 mm²101 A78 A0.77 V (3.21%)23.2 V1.27 V (5.29%)11.6 W~ ≤5%
35 mm²125 A97 A0.55 V (2.29%)23.4 V0.91 V (3.78%)8.3 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (1.61%)23.6 V0.64 V (2.65%)5.8 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (1.15%)23.7 V0.45 V (1.89%)4.1 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.84%)23.8 V0.33 V (1.39%)3.0 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.67%)23.8 V0.26 V (1.1%)2.4 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.53%)23.9 V0.21 V (0.88%)1.9 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.43%)23.9 V0.17 V (0.72%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.33%)23.9 V0.13 V (0.55%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.27%)23.9 V0.11 V (0.44%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.2%)24.0 V0.08 V (0.33%)0.7 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 15A at 30 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 15A over 30m at 24V (voltage drop: 0.55V or 2.29%).

What is the power capacity of 15A at 24V?

At unity power factor, 15A at 24V supports 0.36 kW with a standard 15A circuit breaker.