15 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 0.54V (2.23%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 0.53V (2.21%)
Voltage at Load23.5 VLine Loss: 8.0 W
Max Power & Breaker0.36 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.14 V (8.92%)21.9 V3.53 V (14.71%)32.1 WDrop High
2.5 mm²24 A18 A1.28 V (5.35%)22.7 V2.12 V (8.82%)19.3 WDrop High
4 mm²32 A25 A0.8 V (3.34%)23.2 V1.32 V (5.52%)12.0 W~ ≤5%
6 mm²41 A32 A0.54 V (2.23%)23.5 V0.88 V (3.68%)8.0 W✓ OK (≤3%)
10 mm²57 A44 A0.32 V (1.34%)23.7 V0.53 V (2.21%)4.8 W✓ OK (≤3%)
16 mm²76 A59 A0.2 V (0.84%)23.8 V0.33 V (1.38%)3.0 W✓ OK (≤3%)
25 mm²101 A78 A0.13 V (0.53%)23.9 V0.21 V (0.88%)1.9 W✓ OK (≤3%)
35 mm²125 A97 A0.09 V (0.38%)23.9 V0.15 V (0.63%)1.4 W✓ OK (≤3%)
50 mm²151 A118 A0.06 V (0.27%)23.9 V0.11 V (0.44%)1.0 W✓ OK (≤3%)
70 mm²192 A150 A0.05 V (0.19%)24.0 V0.08 V (0.32%)0.7 W✓ OK (≤3%)
95 mm²232 A181 A0.03 V (0.14%)24.0 V0.06 V (0.23%)0.5 W✓ OK (≤3%)
120 mm²269 A210 A0.03 V (0.11%)24.0 V0.04 V (0.18%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.09%)24.0 V0.04 V (0.15%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.07%)24.0 V0.03 V (0.12%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.01 V (0.06%)24.0 V0.02 V (0.09%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.04%)24.0 V0.02 V (0.07%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.03%)24.0 V0.01 V (0.06%)0.1 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 15A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 15A over 5m at 24V (voltage drop: 0.54V or 2.23%).

What is the power capacity of 15A at 24V?

At unity power factor, 15A at 24V supports 0.36 kW with a standard 15A circuit breaker.