16 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 1.14V (2.38%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.13V (2.35%)
Voltage at Load46.9 VLine Loss: 18.3 W
Max Power & Breaker0.77 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.57 V (9.51%)43.4 V7.53 V (15.69%)73.0 WDrop High
2.5 mm²24 A18 A2.74 V (5.71%)45.3 V4.52 V (9.41%)43.8 WDrop High
4 mm²32 A25 A1.71 V (3.57%)46.3 V2.82 V (5.88%)27.4 W~ ≤5%
6 mm²41 A32 A1.14 V (2.38%)46.9 V1.88 V (3.92%)18.3 W✓ OK (≤3%)
10 mm²57 A44 A0.68 V (1.43%)47.3 V1.13 V (2.35%)11.0 W✓ OK (≤3%)
16 mm²76 A59 A0.43 V (0.89%)47.6 V0.71 V (1.47%)6.8 W✓ OK (≤3%)
25 mm²101 A78 A0.27 V (0.57%)47.7 V0.45 V (0.94%)4.4 W✓ OK (≤3%)
35 mm²125 A97 A0.2 V (0.41%)47.8 V0.32 V (0.67%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.14 V (0.29%)47.9 V0.23 V (0.47%)2.2 W✓ OK (≤3%)
70 mm²192 A150 A0.1 V (0.2%)47.9 V0.16 V (0.34%)1.6 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.15%)47.9 V0.12 V (0.25%)1.2 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.12%)47.9 V0.09 V (0.2%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.1%)48.0 V0.08 V (0.16%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.08%)48.0 V0.06 V (0.13%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.06%)48.0 V0.05 V (0.1%)0.5 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.05%)48.0 V0.04 V (0.08%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.04%)48.0 V0.03 V (0.06%)0.3 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 16A at 10 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 16A over 10m at 48V (voltage drop: 1.14V or 2.38%).

What is the power capacity of 16A at 48V?

At unity power factor, 16A at 48V supports 0.77 kW with a standard 16A circuit breaker.