10 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 10 m (32.8 ft).
Copper Cable (≤3% Drop)4 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 1.18V (2.45%)
Voltage at Load46.9 VLine Loss: 10.7 W
Max Power & Breaker0.48 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2.85 V (5.94%) | 45.1 V | 4.71 V (9.81%) | 28.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1.71 V (3.57%) | 46.3 V | 2.82 V (5.88%) | 17.1 W | ~ ≤5% |
| 4 mm² | 32 A | 25 A | 1.07 V (2.23%) | 46.9 V | 1.76 V (3.68%) | 10.7 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 0.71 V (1.49%) | 47.3 V | 1.18 V (2.45%) | 7.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.43 V (0.89%) | 47.6 V | 0.71 V (1.47%) | 4.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.27 V (0.56%) | 47.7 V | 0.44 V (0.92%) | 2.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.17 V (0.36%) | 47.8 V | 0.28 V (0.59%) | 1.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.12 V (0.25%) | 47.9 V | 0.2 V (0.42%) | 1.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.09 V (0.18%) | 47.9 V | 0.14 V (0.29%) | 0.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.06 V (0.13%) | 47.9 V | 0.1 V (0.21%) | 0.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.05 V (0.09%) | 48.0 V | 0.07 V (0.15%) | 0.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.04 V (0.07%) | 48.0 V | 0.06 V (0.12%) | 0.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.03 V (0.06%) | 48.0 V | 0.05 V (0.1%) | 0.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.02 V (0.05%) | 48.0 V | 0.04 V (0.08%) | 0.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.02 V (0.04%) | 48.0 V | 0.03 V (0.06%) | 0.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.01 V (0.03%) | 48.0 V | 0.02 V (0.05%) | 0.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.01 V (0.02%) | 48.0 V | 0.02 V (0.04%) | 0.1 W | ✓ OK (≤3%) |
FAQ — 10 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 10A at 10 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 10A over 10m at 48V (voltage drop: 1.07V or 2.23%).
What is the power capacity of 10A at 48V?
At unity power factor, 10A at 48V supports 0.48 kW with a standard 10A circuit breaker.
Related Lengths & Currents (48V)
10A · 5m (48V)10A · 15m (48V)10A · 20m (48V)10A · 25m (48V)10A · 30m (48V)10A · 35m (48V)10A · 40m (48V)10A · 45m (48V)10A · 50m (48V)10A · 60m (48V)10A · 70m (48V)16A · 10m (48V)20A · 10m (48V)25A · 10m (48V)32A · 10m (48V)40A · 10m (48V)50A · 10m (48V)63A · 10m (48V)80A · 10m (48V)100A · 10m (48V)125A · 10m (48V)160A · 10m (48V)200A · 10m (48V)