⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 8.9V (2.14%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.17V (2.21%)
Voltage at Load406.1 VLine Loss: 246.5 W
Max Power & Breaker11.5 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.29%)355.7 V97.83 V (23.57%)1643.5 WDrop High
2.5 mm²24 A18 A35.58 V (8.57%)379.4 V58.7 V (14.14%)986.1 WDrop High
4 mm²32 A25 A22.24 V (5.36%)392.8 V36.68 V (8.84%)616.3 WDrop High
6 mm²41 A32 A14.83 V (3.57%)400.2 V24.46 V (5.89%)410.9 W~ ≤5%
10 mm²57 A44 A8.9 V (2.14%)406.1 V14.67 V (3.54%)246.5 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (1.34%)409.4 V9.17 V (2.21%)154.1 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.86%)411.4 V5.87 V (1.41%)98.6 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.61%)412.5 V4.19 V (1.01%)70.4 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.43%)413.2 V2.93 V (0.71%)49.3 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.31%)413.7 V2.1 V (0.51%)35.2 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)414.1 V1.54 V (0.37%)26.0 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.18%)414.3 V1.22 V (0.29%)20.5 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.14%)414.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)414.5 V0.79 V (0.19%)13.3 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)414.6 V0.61 V (0.15%)10.3 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)414.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.05%)414.8 V0.37 V (0.09%)6.2 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 16A at 150 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 16A over 150m at 415V (voltage drop: 8.9V or 2.14%).

What is the power capacity of 16A at 415V?

At unity power factor, 16A at 415V supports 11.5 kW with a standard 16A circuit breaker.