⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 9.88V (2.38%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 9.78V (2.36%)
Voltage at Load405.1 VLine Loss: 273.9 W
Max Power & Breaker11.5 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.88 V (2.38%)405.1 V16.3 V (3.93%)273.9 W✓ OK (≤3%)
2.5 mm²24 A18 A5.93 V (1.43%)409.1 V9.78 V (2.36%)164.4 W✓ OK (≤3%)
4 mm²32 A25 A3.71 V (0.89%)411.3 V6.11 V (1.47%)102.7 W✓ OK (≤3%)
6 mm²41 A32 A2.47 V (0.6%)412.5 V4.08 V (0.98%)68.5 W✓ OK (≤3%)
10 mm²57 A44 A1.48 V (0.36%)413.5 V2.45 V (0.59%)41.1 W✓ OK (≤3%)
16 mm²76 A59 A0.93 V (0.22%)414.1 V1.53 V (0.37%)25.7 W✓ OK (≤3%)
25 mm²101 A78 A0.59 V (0.14%)414.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
35 mm²125 A97 A0.42 V (0.1%)414.6 V0.7 V (0.17%)11.7 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.07%)414.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.05%)414.8 V0.35 V (0.08%)5.9 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.04%)414.8 V0.26 V (0.06%)4.3 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.03%)414.9 V0.2 V (0.05%)3.4 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.02%)414.9 V0.16 V (0.04%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.02%)414.9 V0.13 V (0.03%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.01%)414.9 V0.1 V (0.02%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)415.0 V0.08 V (0.02%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)415.0 V0.06 V (0.01%)1.0 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 16A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 16A over 25m at 415V (voltage drop: 9.88V or 2.38%).

What is the power capacity of 16A at 415V?

At unity power factor, 16A at 415V supports 11.5 kW with a standard 16A circuit breaker.