⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 14.83V (2.15%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 14.67V (2.13%)
Voltage at Load675.2 VLine Loss: 410.9 W
Max Power & Breaker19.12 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (8.59%)630.7 V97.83 V (14.18%)1643.5 WDrop High
2.5 mm²24 A18 A35.58 V (5.16%)654.4 V58.7 V (8.51%)986.1 WDrop High
4 mm²32 A25 A22.24 V (3.22%)667.8 V36.68 V (5.32%)616.3 W~ ≤5%
6 mm²41 A32 A14.83 V (2.15%)675.2 V24.46 V (3.54%)410.9 W✓ OK (≤3%)
10 mm²57 A44 A8.9 V (1.29%)681.1 V14.67 V (2.13%)246.5 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (0.81%)684.4 V9.17 V (1.33%)154.1 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.52%)686.4 V5.87 V (0.85%)98.6 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.37%)687.5 V4.19 V (0.61%)70.4 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.26%)688.2 V2.93 V (0.43%)49.3 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.18%)688.7 V2.1 V (0.3%)35.2 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.14%)689.1 V1.54 V (0.22%)26.0 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.11%)689.3 V1.22 V (0.18%)20.5 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.09%)689.4 V0.98 V (0.14%)16.4 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.07%)689.5 V0.79 V (0.11%)13.3 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.05%)689.6 V0.61 V (0.09%)10.3 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.04%)689.7 V0.49 V (0.07%)8.2 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.03%)689.8 V0.37 V (0.05%)6.2 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 16A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 16A over 150m at 690V (voltage drop: 14.83V or 2.15%).

What is the power capacity of 16A at 690V?

At unity power factor, 16A at 690V supports 19.12 kW with a standard 16A circuit breaker.