16 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 15 m (49.2 ft).
Copper Cable (≤3% Drop)1.5 mm²Drop: 5.93V (0.86%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 5.87V (0.85%)
Voltage at Load684.1 VLine Loss: 164.4 W
Max Power & Breaker19.12 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 5.93 V (0.86%) | 684.1 V | 9.78 V (1.42%) | 164.4 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 3.56 V (0.52%) | 686.4 V | 5.87 V (0.85%) | 98.6 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 2.22 V (0.32%) | 687.8 V | 3.67 V (0.53%) | 61.6 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 1.48 V (0.21%) | 688.5 V | 2.45 V (0.35%) | 41.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.89 V (0.13%) | 689.1 V | 1.47 V (0.21%) | 24.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.56 V (0.08%) | 689.4 V | 0.92 V (0.13%) | 15.4 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.36 V (0.05%) | 689.6 V | 0.59 V (0.09%) | 9.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.25 V (0.04%) | 689.7 V | 0.42 V (0.06%) | 7.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.18 V (0.03%) | 689.8 V | 0.29 V (0.04%) | 4.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.13 V (0.02%) | 689.9 V | 0.21 V (0.03%) | 3.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.09 V (0.01%) | 689.9 V | 0.15 V (0.02%) | 2.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.07 V (0.01%) | 689.9 V | 0.12 V (0.02%) | 2.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.06 V (0.01%) | 689.9 V | 0.1 V (0.01%) | 1.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.05 V (0.01%) | 690.0 V | 0.08 V (0.01%) | 1.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.04 V (0.01%) | 690.0 V | 0.06 V (0.01%) | 1.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.03 V (0.0%) | 690.0 V | 0.05 V (0.01%) | 0.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.02 V (0.0%) | 690.0 V | 0.04 V (0.01%) | 0.6 W | ✓ OK (≤3%) |
FAQ — 16 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 16A at 15 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 16A over 15m at 690V (voltage drop: 5.93V or 0.86%).
What is the power capacity of 16A at 690V?
At unity power factor, 16A at 690V supports 19.12 kW with a standard 16A circuit breaker.
Related Lengths & Currents (690V)
16A · 5m (690V)16A · 10m (690V)16A · 20m (690V)16A · 25m (690V)16A · 30m (690V)16A · 35m (690V)16A · 40m (690V)16A · 45m (690V)16A · 50m (690V)16A · 60m (690V)16A · 70m (690V)10A · 15m (690V)20A · 15m (690V)25A · 15m (690V)32A · 15m (690V)40A · 15m (690V)50A · 15m (690V)63A · 15m (690V)80A · 15m (690V)100A · 15m (690V)125A · 15m (690V)160A · 15m (690V)200A · 15m (690V)