125 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 3.31V (0.8%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.73V (0.66%)
Voltage at Load411.7 VLine Loss: 716.5 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.22 V (18.61%)337.8 V127.38 V (30.69%)16718.8 WDrop High
2.5 mm²24 A18 A46.33 V (11.16%)368.7 V76.43 V (18.42%)10031.2 WDrop High
4 mm²32 A25 A28.96 V (6.98%)386.0 V47.77 V (11.51%)6269.5 WDrop High
6 mm²41 A32 A19.31 V (4.65%)395.7 V31.84 V (7.67%)4179.7 WDrop High
10 mm²57 A44 A11.58 V (2.79%)403.4 V19.11 V (4.6%)2507.8 WDrop High
16 mm²76 A59 A7.24 V (1.74%)407.8 V11.94 V (2.88%)1567.4 WDrop High
25 mm²101 A78 A4.63 V (1.12%)410.4 V7.64 V (1.84%)1003.1 WDrop High
35 mm²125 A97 A3.31 V (0.8%)411.7 V5.46 V (1.32%)716.5 W✓ OK (≤3%)
50 mm²151 A118 A2.32 V (0.56%)412.7 V3.82 V (0.92%)501.6 W✓ OK (≤3%)
70 mm²192 A150 A1.65 V (0.4%)413.3 V2.73 V (0.66%)358.3 W✓ OK (≤3%)
95 mm²232 A181 A1.22 V (0.29%)413.8 V2.01 V (0.48%)264.0 W✓ OK (≤3%)
120 mm²269 A210 A0.97 V (0.23%)414.0 V1.59 V (0.38%)209.0 W✓ OK (≤3%)
150 mm²309 A241 A0.77 V (0.19%)414.2 V1.27 V (0.31%)167.2 W✓ OK (≤3%)
185 mm²353 A275 A0.63 V (0.15%)414.4 V1.03 V (0.25%)135.6 W✓ OK (≤3%)
240 mm²415 A324 A0.48 V (0.12%)414.5 V0.8 V (0.19%)104.5 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.09%)414.6 V0.64 V (0.15%)83.6 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.07%)414.7 V0.48 V (0.12%)62.7 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 25m at 415V (voltage drop: 3.31V or 0.8%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.