16 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.37V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.69V (3.53%)
Voltage at Load46.6 VLine Loss: 21.9 W
Max Power & Breaker0.77 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A273.92 V (570.67%)0.0 V451.84 V (941.33%)4382.7 WDrop High
2.5 mm²24 A18 A164.35 V (342.4%)0.0 V271.1 V (564.8%)2629.6 WDrop High
4 mm²32 A25 A102.72 V (214.0%)0.0 V169.44 V (353.0%)1643.5 WDrop High
6 mm²41 A32 A68.48 V (142.67%)0.0 V112.96 V (235.33%)1095.7 WDrop High
10 mm²57 A44 A41.09 V (85.6%)6.9 V67.78 V (141.2%)657.4 WDrop High
16 mm²76 A59 A25.68 V (53.5%)22.3 V42.36 V (88.25%)410.9 WDrop High
25 mm²101 A78 A16.44 V (34.24%)31.6 V27.11 V (56.48%)263.0 WDrop High
35 mm²125 A97 A11.74 V (24.46%)36.3 V19.36 V (40.34%)187.8 WDrop High
50 mm²151 A118 A8.22 V (17.12%)39.8 V13.56 V (28.24%)131.5 WDrop High
70 mm²192 A150 A5.87 V (12.23%)42.1 V9.68 V (20.17%)93.9 WDrop High
95 mm²232 A181 A4.33 V (9.01%)43.7 V7.13 V (14.86%)69.2 WDrop High
120 mm²269 A210 A3.42 V (7.13%)44.6 V5.65 V (11.77%)54.8 WDrop High
150 mm²309 A241 A2.74 V (5.71%)45.3 V4.52 V (9.41%)43.8 WDrop High
185 mm²353 A275 A2.22 V (4.63%)45.8 V3.66 V (7.63%)35.5 W~ ≤5%
240 mm²415 A324 A1.71 V (3.57%)46.3 V2.82 V (5.88%)27.4 W~ ≤5%
300 mm²477 A372 A1.37 V (2.85%)46.6 V2.26 V (4.71%)21.9 W✓ OK (≤3%)
400 mm²570 A445 A1.03 V (2.14%)47.0 V1.69 V (3.53%)16.4 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 16A at 600 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 16A over 600m at 48V (voltage drop: 1.37V or 2.85%).

What is the power capacity of 16A at 48V?

At unity power factor, 16A at 48V supports 0.77 kW with a standard 16A circuit breaker.