160 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 1.18V (2.45%)
Voltage at Load46.6 VLine Loss: 228.3 W
Max Power & Breaker7.68 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A114.13 V (237.78%)0.0 V188.27 V (392.22%)18261.3 WDrop High
2.5 mm²24 A18 A68.48 V (142.67%)0.0 V112.96 V (235.33%)10956.8 WDrop High
4 mm²32 A25 A42.8 V (89.17%)5.2 V70.6 V (147.08%)6848.0 WDrop High
6 mm²41 A32 A28.53 V (59.44%)19.5 V47.07 V (98.06%)4565.3 WDrop High
10 mm²57 A44 A17.12 V (35.67%)30.9 V28.24 V (58.83%)2739.2 WDrop High
16 mm²76 A59 A10.7 V (22.29%)37.3 V17.65 V (36.77%)1712.0 WDrop High
25 mm²101 A78 A6.85 V (14.27%)41.2 V11.3 V (23.53%)1095.7 WDrop High
35 mm²125 A97 A4.89 V (10.19%)43.1 V8.07 V (16.81%)782.6 WDrop High
50 mm²151 A118 A3.42 V (7.13%)44.6 V5.65 V (11.77%)547.8 WDrop High
70 mm²192 A150 A2.45 V (5.1%)45.6 V4.03 V (8.4%)391.3 WDrop High
95 mm²232 A181 A1.8 V (3.75%)46.2 V2.97 V (6.19%)288.3 W~ ≤5%
120 mm²269 A210 A1.43 V (2.97%)46.6 V2.35 V (4.9%)228.3 W✓ OK (≤3%)
150 mm²309 A241 A1.14 V (2.38%)46.9 V1.88 V (3.92%)182.6 W✓ OK (≤3%)
185 mm²353 A275 A0.93 V (1.93%)47.1 V1.53 V (3.18%)148.1 W✓ OK (≤3%)
240 mm²415 A324 A0.71 V (1.49%)47.3 V1.18 V (2.45%)114.1 W✓ OK (≤3%)
300 mm²477 A372 A0.57 V (1.19%)47.4 V0.94 V (1.96%)91.3 W✓ OK (≤3%)
400 mm²570 A445 A0.43 V (0.89%)47.6 V0.71 V (1.47%)68.5 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 160A at 25 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 160A over 25m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 160A at 48V?

At unity power factor, 160A at 48V supports 7.68 kW with a standard 160A circuit breaker.