125 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.41V (2.93%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 1.19V (2.48%)
Voltage at Load46.6 VLine Loss: 176.0 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A89.17 V (185.76%)0.0 V147.08 V (306.42%)11145.8 WDrop High
2.5 mm²24 A18 A53.5 V (111.46%)0.0 V88.25 V (183.85%)6687.5 WDrop High
4 mm²32 A25 A33.44 V (69.66%)14.6 V55.16 V (114.91%)4179.7 WDrop High
6 mm²41 A32 A22.29 V (46.44%)25.7 V36.77 V (76.61%)2786.5 WDrop High
10 mm²57 A44 A13.37 V (27.86%)34.6 V22.06 V (45.96%)1671.9 WDrop High
16 mm²76 A59 A8.36 V (17.42%)39.6 V13.79 V (28.73%)1044.9 WDrop High
25 mm²101 A78 A5.35 V (11.15%)42.6 V8.82 V (18.39%)668.7 WDrop High
35 mm²125 A97 A3.82 V (7.96%)44.2 V6.3 V (13.13%)477.7 WDrop High
50 mm²151 A118 A2.67 V (5.57%)45.3 V4.41 V (9.19%)334.4 WDrop High
70 mm²192 A150 A1.91 V (3.98%)46.1 V3.15 V (6.57%)238.8 W~ ≤5%
95 mm²232 A181 A1.41 V (2.93%)46.6 V2.32 V (4.84%)176.0 W✓ OK (≤3%)
120 mm²269 A210 A1.11 V (2.32%)46.9 V1.84 V (3.83%)139.3 W✓ OK (≤3%)
150 mm²309 A241 A0.89 V (1.86%)47.1 V1.47 V (3.06%)111.5 W✓ OK (≤3%)
185 mm²353 A275 A0.72 V (1.51%)47.3 V1.19 V (2.48%)90.4 W✓ OK (≤3%)
240 mm²415 A324 A0.56 V (1.16%)47.4 V0.92 V (1.92%)69.7 W✓ OK (≤3%)
300 mm²477 A372 A0.45 V (0.93%)47.6 V0.74 V (1.53%)55.7 W✓ OK (≤3%)
400 mm²570 A445 A0.33 V (0.7%)47.7 V0.55 V (1.15%)41.8 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 25 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 125A over 25m at 48V (voltage drop: 1.41V or 2.93%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.