⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

160 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 15.61V (2.26%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 20.38V (2.95%)
Voltage at Load674.4 VLine Loss: 4325.1 W
Max Power & Breaker191.22 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (143.25%)0.0 V1630.44 V (236.3%)273920.0 WDrop High
2.5 mm²24 A18 A593.05 V (85.95%)96.9 V978.26 V (141.78%)164352.0 WDrop High
4 mm²32 A25 A370.66 V (53.72%)319.3 V611.41 V (88.61%)102720.0 WDrop High
6 mm²41 A32 A247.11 V (35.81%)442.9 V407.61 V (59.07%)68480.0 WDrop High
10 mm²57 A44 A148.26 V (21.49%)541.7 V244.57 V (35.44%)41088.0 WDrop High
16 mm²76 A59 A92.66 V (13.43%)597.3 V152.85 V (22.15%)25680.0 WDrop High
25 mm²101 A78 A59.31 V (8.59%)630.7 V97.83 V (14.18%)16435.2 WDrop High
35 mm²125 A97 A42.36 V (6.14%)647.6 V69.88 V (10.13%)11739.4 WDrop High
50 mm²151 A118 A29.65 V (4.3%)660.3 V48.91 V (7.09%)8217.6 WDrop High
70 mm²192 A150 A21.18 V (3.07%)668.8 V34.94 V (5.06%)5869.7 W~ ≤5%
95 mm²232 A181 A15.61 V (2.26%)674.4 V25.74 V (3.73%)4325.1 W✓ OK (≤3%)
120 mm²269 A210 A12.36 V (1.79%)677.6 V20.38 V (2.95%)3424.0 W✓ OK (≤3%)
150 mm²309 A241 A9.88 V (1.43%)680.1 V16.3 V (2.36%)2739.2 W✓ OK (≤3%)
185 mm²353 A275 A8.01 V (1.16%)682.0 V13.22 V (1.92%)2221.0 W✓ OK (≤3%)
240 mm²415 A324 A6.18 V (0.9%)683.8 V10.19 V (1.48%)1712.0 W✓ OK (≤3%)
300 mm²477 A372 A4.94 V (0.72%)685.1 V8.15 V (1.18%)1369.6 W✓ OK (≤3%)
400 mm²570 A445 A3.71 V (0.54%)686.3 V6.11 V (0.89%)1027.2 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 160A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 160A over 250m at 690V (voltage drop: 15.61V or 2.26%).

What is the power capacity of 160A at 690V?

At unity power factor, 160A at 690V supports 191.22 kW with a standard 160A circuit breaker.