125 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 16.55V (2.4%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 20.11V (2.91%)
Voltage at Load673.5 VLine Loss: 3582.6 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A772.21 V (111.91%)0.0 V1273.78 V (184.61%)167187.5 WDrop High
2.5 mm²24 A18 A463.32 V (67.15%)226.7 V764.27 V (110.76%)100312.5 WDrop High
4 mm²32 A25 A289.58 V (41.97%)400.4 V477.67 V (69.23%)62695.3 WDrop High
6 mm²41 A32 A193.05 V (27.98%)496.9 V318.44 V (46.15%)41796.9 WDrop High
10 mm²57 A44 A115.83 V (16.79%)574.2 V191.07 V (27.69%)25078.1 WDrop High
16 mm²76 A59 A72.39 V (10.49%)617.6 V119.42 V (17.31%)15673.8 WDrop High
25 mm²101 A78 A46.33 V (6.71%)643.7 V76.43 V (11.08%)10031.2 WDrop High
35 mm²125 A97 A33.09 V (4.8%)656.9 V54.59 V (7.91%)7165.2 W~ ≤5%
50 mm²151 A118 A23.17 V (3.36%)666.8 V38.21 V (5.54%)5015.6 W~ ≤5%
70 mm²192 A150 A16.55 V (2.4%)673.5 V27.3 V (3.96%)3582.6 W✓ OK (≤3%)
95 mm²232 A181 A12.19 V (1.77%)677.8 V20.11 V (2.91%)2639.8 W✓ OK (≤3%)
120 mm²269 A210 A9.65 V (1.4%)680.3 V15.92 V (2.31%)2089.8 W✓ OK (≤3%)
150 mm²309 A241 A7.72 V (1.12%)682.3 V12.74 V (1.85%)1671.9 W✓ OK (≤3%)
185 mm²353 A275 A6.26 V (0.91%)683.7 V10.33 V (1.5%)1355.6 W✓ OK (≤3%)
240 mm²415 A324 A4.83 V (0.7%)685.2 V7.96 V (1.15%)1044.9 W✓ OK (≤3%)
300 mm²477 A372 A3.86 V (0.56%)686.1 V6.37 V (0.92%)835.9 W✓ OK (≤3%)
400 mm²570 A445 A2.9 V (0.42%)687.1 V4.78 V (0.69%)627.0 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 125A over 250m at 690V (voltage drop: 16.55V or 2.4%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.