160 Amp Cable Size at 400 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.3V (4.91%)
Voltage at Load223.2 VLine Loss: 1095.7 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1826.13 V (793.97%)0.0 V3012.27 V (1309.68%)292181.3 WDrop High
2.5 mm²24 A18 A1095.68 V (476.38%)0.0 V1807.36 V (785.81%)175308.8 WDrop High
4 mm²32 A25 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)109568.0 WDrop High
6 mm²41 A32 A456.53 V (198.49%)0.0 V753.07 V (327.42%)73045.3 WDrop High
10 mm²57 A44 A273.92 V (119.1%)0.0 V451.84 V (196.45%)43827.2 WDrop High
16 mm²76 A59 A171.2 V (74.43%)58.8 V282.4 V (122.78%)27392.0 WDrop High
25 mm²101 A78 A109.57 V (47.64%)120.4 V180.74 V (78.58%)17530.9 WDrop High
35 mm²125 A97 A78.26 V (34.03%)151.7 V129.1 V (56.13%)12522.1 WDrop High
50 mm²151 A118 A54.78 V (23.82%)175.2 V90.37 V (39.29%)8765.4 WDrop High
70 mm²192 A150 A39.13 V (17.01%)190.9 V64.55 V (28.06%)6261.0 WDrop High
95 mm²232 A181 A28.83 V (12.54%)201.2 V47.56 V (20.68%)4613.4 WDrop High
120 mm²269 A210 A22.83 V (9.92%)207.2 V37.65 V (16.37%)3652.3 WDrop High
150 mm²309 A241 A18.26 V (7.94%)211.7 V30.12 V (13.1%)2921.8 WDrop High
185 mm²353 A275 A14.81 V (6.44%)215.2 V24.42 V (10.62%)2369.0 WDrop High
240 mm²415 A324 A11.41 V (4.96%)218.6 V18.83 V (8.19%)1826.1 W~ ≤5%
300 mm²477 A372 A9.13 V (3.97%)220.9 V15.06 V (6.55%)1460.9 W~ ≤5%
400 mm²570 A445 A6.85 V (2.98%)223.2 V11.3 V (4.91%)1095.7 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 400 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 160A at 400 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 160A over 400m at 230V (voltage drop: 6.85V or 2.98%).

What is the power capacity of 160A at 230V?

At unity power factor, 160A at 230V supports 36.8 kW with a standard 160A circuit breaker.