⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

160 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 0.49V (0.21%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.59V (0.26%)
Voltage at Load229.5 VLine Loss: 78.3 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.83 V (9.92%)207.2 V37.65 V (16.37%)3652.3 WDrop High
2.5 mm²24 A18 A13.7 V (5.95%)216.3 V22.59 V (9.82%)2191.4 WDrop High
4 mm²32 A25 A8.56 V (3.72%)221.4 V14.12 V (6.14%)1369.6 WDrop High
6 mm²41 A32 A5.71 V (2.48%)224.3 V9.41 V (4.09%)913.1 WDrop High
10 mm²57 A44 A3.42 V (1.49%)226.6 V5.65 V (2.46%)547.8 WDrop High
16 mm²76 A59 A2.14 V (0.93%)227.9 V3.53 V (1.53%)342.4 WDrop High
25 mm²101 A78 A1.37 V (0.6%)228.6 V2.26 V (0.98%)219.1 WDrop High
35 mm²125 A97 A0.98 V (0.43%)229.0 V1.61 V (0.7%)156.5 WDrop High
50 mm²151 A118 A0.68 V (0.3%)229.3 V1.13 V (0.49%)109.6 WDrop High
70 mm²192 A150 A0.49 V (0.21%)229.5 V0.81 V (0.35%)78.3 W✓ OK (≤3%)
95 mm²232 A181 A0.36 V (0.16%)229.6 V0.59 V (0.26%)57.7 W✓ OK (≤3%)
120 mm²269 A210 A0.29 V (0.12%)229.7 V0.47 V (0.2%)45.7 W✓ OK (≤3%)
150 mm²309 A241 A0.23 V (0.1%)229.8 V0.38 V (0.16%)36.5 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.08%)229.8 V0.31 V (0.13%)29.6 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.06%)229.9 V0.24 V (0.1%)22.8 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.05%)229.9 V0.19 V (0.08%)18.3 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.04%)229.9 V0.14 V (0.06%)13.7 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 160A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 160A over 5m at 230V (voltage drop: 0.49V or 0.21%).

What is the power capacity of 160A at 230V?

At unity power factor, 160A at 230V supports 36.8 kW with a standard 160A circuit breaker.