10 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 5 m (16.4 ft).
Copper Cable (≤3% Drop)1.5 mm²Drop: 1.43V (0.62%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 2.35V (1.02%)
Voltage at Load228.6 VLine Loss: 14.3 W
Max Power & Breaker2.3 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1.43 V (0.62%) | 228.6 V | 2.35 V (1.02%) | 14.3 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 0.86 V (0.37%) | 229.1 V | 1.41 V (0.61%) | 8.6 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 0.54 V (0.23%) | 229.5 V | 0.88 V (0.38%) | 5.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 0.36 V (0.16%) | 229.6 V | 0.59 V (0.26%) | 3.6 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.21 V (0.09%) | 229.8 V | 0.35 V (0.15%) | 2.1 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.13 V (0.06%) | 229.9 V | 0.22 V (0.1%) | 1.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.09 V (0.04%) | 229.9 V | 0.14 V (0.06%) | 0.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.06 V (0.03%) | 229.9 V | 0.1 V (0.04%) | 0.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 0.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.03 V (0.01%) | 230.0 V | 0.05 V (0.02%) | 0.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.02 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.02 V (0.01%) | 230.0 V | 0.03 V (0.01%) | 0.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.01 V (0.01%) | 230.0 V | 0.02 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.01 V (0.01%) | 230.0 V | 0.02 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.01 V (0.0%) | 230.0 V | 0.01 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.01 V (0.0%) | 230.0 V | 0.01 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.01 V (0.0%) | 230.0 V | 0.01 V (0.0%) | 0.1 W | ✓ OK (≤3%) |
FAQ — 10 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 10A at 5 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 10A over 5m at 230V (voltage drop: 1.43V or 0.62%).
What is the power capacity of 10A at 230V?
At unity power factor, 10A at 230V supports 2.3 kW with a standard 10A circuit breaker.
Related Lengths & Currents (230V)
10A · 10m (230V)10A · 15m (230V)10A · 20m (230V)10A · 25m (230V)10A · 30m (230V)10A · 35m (230V)10A · 40m (230V)10A · 45m (230V)10A · 50m (230V)10A · 60m (230V)10A · 70m (230V)16A · 5m (230V)20A · 5m (230V)25A · 5m (230V)32A · 5m (230V)40A · 5m (230V)50A · 5m (230V)63A · 5m (230V)80A · 5m (230V)100A · 5m (230V)125A · 5m (230V)160A · 5m (230V)200A · 5m (230V)