160 Amp Cable Size at 600 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 600 m (1968.5 ft).
Copper Cable (≤3% Drop)15× 400 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.94V (70.6%)
Voltage at Load23.3 VLine Loss: 109.6 W
Max Power & Breaker3.84 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2739.2 V (11413.33%) | 0.0 V | 4518.4 V (18826.67%) | 438272.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1643.52 V (6848.0%) | 0.0 V | 2711.04 V (11296.0%) | 262963.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 1027.2 V (4280.0%) | 0.0 V | 1694.4 V (7060.0%) | 164352.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 684.8 V (2853.33%) | 0.0 V | 1129.6 V (4706.67%) | 109568.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 410.88 V (1712.0%) | 0.0 V | 677.76 V (2824.0%) | 65740.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 256.8 V (1070.0%) | 0.0 V | 423.6 V (1765.0%) | 41088.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 164.35 V (684.8%) | 0.0 V | 271.1 V (1129.6%) | 26296.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 117.39 V (489.14%) | 0.0 V | 193.65 V (806.86%) | 18783.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 82.18 V (342.4%) | 0.0 V | 135.55 V (564.8%) | 13148.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 58.7 V (244.57%) | 0.0 V | 96.82 V (403.43%) | 9391.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 43.25 V (180.21%) | 0.0 V | 71.34 V (297.26%) | 6920.1 W | Drop High |
| 120 mm² | 269 A | 210 A | 34.24 V (142.67%) | 0.0 V | 56.48 V (235.33%) | 5478.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 27.39 V (114.13%) | 0.0 V | 45.18 V (188.27%) | 4382.7 W | Drop High |
| 185 mm² | 353 A | 275 A | 22.21 V (92.54%) | 1.8 V | 36.64 V (152.65%) | 3553.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 17.12 V (71.33%) | 6.9 V | 28.24 V (117.67%) | 2739.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 13.7 V (57.07%) | 10.3 V | 22.59 V (94.13%) | 2191.4 W | Drop High |
| 400 mm² | 570 A | 445 A | 10.27 V (42.8%) | 13.7 V | 16.94 V (70.6%) | 1643.5 W | Drop High |
FAQ — 160 Amp Cable Size at 600 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 160A at 600 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 15× 400 mm² copper cable for 160A over 600m at 24V (voltage drop: 0.68V or 2.85%).
What is the power capacity of 160A at 24V?
At unity power factor, 160A at 24V supports 3.84 kW with a standard 160A circuit breaker.
Related Lengths & Currents (24V)
160A · 5m (24V)160A · 10m (24V)160A · 15m (24V)160A · 20m (24V)160A · 25m (24V)160A · 30m (24V)160A · 35m (24V)160A · 40m (24V)160A · 45m (24V)160A · 50m (24V)160A · 60m (24V)160A · 70m (24V)10A · 600m (24V)16A · 600m (24V)20A · 600m (24V)25A · 600m (24V)32A · 600m (24V)40A · 600m (24V)50A · 600m (24V)63A · 600m (24V)80A · 600m (24V)100A · 600m (24V)125A · 600m (24V)200A · 600m (24V)