175 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.72V (3.36%)
Voltage at Load223.8 VLine Loss: 1092.3 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1248.33 V (542.75%)0.0 V2059.17 V (895.29%)218458.3 WDrop High
2.5 mm²24 A18 A749.0 V (325.65%)0.0 V1235.5 V (537.17%)131075.0 WDrop High
4 mm²32 A25 A468.12 V (203.53%)0.0 V772.19 V (335.73%)81921.9 WDrop High
6 mm²41 A32 A312.08 V (135.69%)0.0 V514.79 V (223.82%)54614.6 WDrop High
10 mm²57 A44 A187.25 V (81.41%)42.8 V308.88 V (134.29%)32768.7 WDrop High
16 mm²76 A59 A117.03 V (50.88%)113.0 V193.05 V (83.93%)20480.5 WDrop High
25 mm²101 A78 A74.9 V (32.57%)155.1 V123.55 V (53.72%)13107.5 WDrop High
35 mm²125 A97 A53.5 V (23.26%)176.5 V88.25 V (38.37%)9362.5 WDrop High
50 mm²151 A118 A37.45 V (16.28%)192.6 V61.77 V (26.86%)6553.8 WDrop High
70 mm²192 A150 A26.75 V (11.63%)203.2 V44.12 V (19.18%)4681.2 WDrop High
95 mm²232 A181 A19.71 V (8.57%)210.3 V32.51 V (14.14%)3449.3 WDrop High
120 mm²269 A210 A15.6 V (6.78%)214.4 V25.74 V (11.19%)2730.7 WDrop High
150 mm²309 A241 A12.48 V (5.43%)217.5 V20.59 V (8.95%)2184.6 WDrop High
185 mm²353 A275 A10.12 V (4.4%)219.9 V16.7 V (7.26%)1771.3 W~ ≤5%
240 mm²415 A324 A7.8 V (3.39%)222.2 V12.87 V (5.6%)1365.4 W~ ≤5%
300 mm²477 A372 A6.24 V (2.71%)223.8 V10.3 V (4.48%)1092.3 W✓ OK (≤3%)
400 mm²570 A445 A4.68 V (2.04%)225.3 V7.72 V (3.36%)819.2 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 175A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 175A over 250m at 230V (voltage drop: 6.24V or 2.71%).

What is the power capacity of 175A at 230V?

At unity power factor, 175A at 230V supports 40.25 kW with a standard 175A circuit breaker.