20 Amp Cable Size at 60 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 1.03V (2.14%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.21V (2.52%)
Voltage at Load47.0 VLine Loss: 20.5 W
Max Power & Breaker0.96 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.24 V (71.33%)13.8 V56.48 V (117.67%)684.8 WDrop High
2.5 mm²24 A18 A20.54 V (42.8%)27.5 V33.89 V (70.6%)410.9 WDrop High
4 mm²32 A25 A12.84 V (26.75%)35.2 V21.18 V (44.12%)256.8 WDrop High
6 mm²41 A32 A8.56 V (17.83%)39.4 V14.12 V (29.42%)171.2 WDrop High
10 mm²57 A44 A5.14 V (10.7%)42.9 V8.47 V (17.65%)102.7 WDrop High
16 mm²76 A59 A3.21 V (6.69%)44.8 V5.29 V (11.03%)64.2 WDrop High
25 mm²101 A78 A2.05 V (4.28%)45.9 V3.39 V (7.06%)41.1 W~ ≤5%
35 mm²125 A97 A1.47 V (3.06%)46.5 V2.42 V (5.04%)29.3 W~ ≤5%
50 mm²151 A118 A1.03 V (2.14%)47.0 V1.69 V (3.53%)20.5 W✓ OK (≤3%)
70 mm²192 A150 A0.73 V (1.53%)47.3 V1.21 V (2.52%)14.7 W✓ OK (≤3%)
95 mm²232 A181 A0.54 V (1.13%)47.5 V0.89 V (1.86%)10.8 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.89%)47.6 V0.71 V (1.47%)8.6 W✓ OK (≤3%)
150 mm²309 A241 A0.34 V (0.71%)47.7 V0.56 V (1.18%)6.8 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.58%)47.7 V0.46 V (0.95%)5.6 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.45%)47.8 V0.35 V (0.74%)4.3 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.36%)47.8 V0.28 V (0.59%)3.4 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.27%)47.9 V0.21 V (0.44%)2.6 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 60 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 20A at 60 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 20A over 60m at 48V (voltage drop: 1.03V or 2.14%).

What is the power capacity of 20A at 48V?

At unity power factor, 20A at 48V supports 0.96 kW with a standard 20A circuit breaker.