20 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 1.1V (2.29%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.27V (2.65%)
Voltage at Load46.9 VLine Loss: 22.0 W
Max Power & Breaker0.96 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A25.68 V (53.5%)22.3 V42.36 V (88.25%)513.6 WDrop High
2.5 mm²24 A18 A15.41 V (32.1%)32.6 V25.42 V (52.95%)308.2 WDrop High
4 mm²32 A25 A9.63 V (20.06%)38.4 V15.88 V (33.09%)192.6 WDrop High
6 mm²41 A32 A6.42 V (13.38%)41.6 V10.59 V (22.06%)128.4 WDrop High
10 mm²57 A44 A3.85 V (8.03%)44.1 V6.35 V (13.24%)77.0 WDrop High
16 mm²76 A59 A2.41 V (5.02%)45.6 V3.97 V (8.27%)48.1 WDrop High
25 mm²101 A78 A1.54 V (3.21%)46.5 V2.54 V (5.29%)30.8 W~ ≤5%
35 mm²125 A97 A1.1 V (2.29%)46.9 V1.82 V (3.78%)22.0 W✓ OK (≤3%)
50 mm²151 A118 A0.77 V (1.6%)47.2 V1.27 V (2.65%)15.4 W✓ OK (≤3%)
70 mm²192 A150 A0.55 V (1.15%)47.4 V0.91 V (1.89%)11.0 W✓ OK (≤3%)
95 mm²232 A181 A0.41 V (0.84%)47.6 V0.67 V (1.39%)8.1 W✓ OK (≤3%)
120 mm²269 A210 A0.32 V (0.67%)47.7 V0.53 V (1.1%)6.4 W✓ OK (≤3%)
150 mm²309 A241 A0.26 V (0.53%)47.7 V0.42 V (0.88%)5.1 W✓ OK (≤3%)
185 mm²353 A275 A0.21 V (0.43%)47.8 V0.34 V (0.72%)4.2 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.33%)47.8 V0.26 V (0.55%)3.2 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.27%)47.9 V0.21 V (0.44%)2.6 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.2%)47.9 V0.16 V (0.33%)1.9 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 20A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 20A over 45m at 48V (voltage drop: 1.1V or 2.29%).

What is the power capacity of 20A at 48V?

At unity power factor, 20A at 48V supports 0.96 kW with a standard 20A circuit breaker.