200 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.18V (2.69%)
Voltage at Load223.8 VLine Loss: 1248.3 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A998.67 V (434.2%)0.0 V1647.33 V (716.23%)199733.3 WDrop High
2.5 mm²24 A18 A599.2 V (260.52%)0.0 V988.4 V (429.74%)119840.0 WDrop High
4 mm²32 A25 A374.5 V (162.83%)0.0 V617.75 V (268.59%)74900.0 WDrop High
6 mm²41 A32 A249.67 V (108.55%)0.0 V411.83 V (179.06%)49933.3 WDrop High
10 mm²57 A44 A149.8 V (65.13%)80.2 V247.1 V (107.43%)29960.0 WDrop High
16 mm²76 A59 A93.62 V (40.71%)136.4 V154.44 V (67.15%)18725.0 WDrop High
25 mm²101 A78 A59.92 V (26.05%)170.1 V98.84 V (42.97%)11984.0 WDrop High
35 mm²125 A97 A42.8 V (18.61%)187.2 V70.6 V (30.7%)8560.0 WDrop High
50 mm²151 A118 A29.96 V (13.03%)200.0 V49.42 V (21.49%)5992.0 WDrop High
70 mm²192 A150 A21.4 V (9.3%)208.6 V35.3 V (15.35%)4280.0 WDrop High
95 mm²232 A181 A15.77 V (6.86%)214.2 V26.01 V (11.31%)3153.7 WDrop High
120 mm²269 A210 A12.48 V (5.43%)217.5 V20.59 V (8.95%)2496.7 WDrop High
150 mm²309 A241 A9.99 V (4.34%)220.0 V16.47 V (7.16%)1997.3 W~ ≤5%
185 mm²353 A275 A8.1 V (3.52%)221.9 V13.36 V (5.81%)1619.5 W~ ≤5%
240 mm²415 A324 A6.24 V (2.71%)223.8 V10.3 V (4.48%)1248.3 W✓ OK (≤3%)
300 mm²477 A372 A4.99 V (2.17%)225.0 V8.24 V (3.58%)998.7 W✓ OK (≤3%)
400 mm²570 A445 A3.74 V (1.63%)226.3 V6.18 V (2.69%)749.0 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 200A at 175 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 200A over 175m at 230V (voltage drop: 6.24V or 2.71%).

What is the power capacity of 200A at 230V?

At unity power factor, 200A at 230V supports 46.0 kW with a standard 200A circuit breaker.