⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

200 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 3.12V (0.75%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 4.08V (0.98%)
Voltage at Load411.9 VLine Loss: 1081.3 W
Max Power & Breaker143.76 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A197.68 V (47.63%)217.3 V326.09 V (78.58%)68480.0 WDrop High
2.5 mm²24 A18 A118.61 V (28.58%)296.4 V195.65 V (47.15%)41088.0 WDrop High
4 mm²32 A25 A74.13 V (17.86%)340.9 V122.28 V (29.47%)25680.0 WDrop High
6 mm²41 A32 A49.42 V (11.91%)365.6 V81.52 V (19.64%)17120.0 WDrop High
10 mm²57 A44 A29.65 V (7.15%)385.3 V48.91 V (11.79%)10272.0 WDrop High
16 mm²76 A59 A18.53 V (4.47%)396.5 V30.57 V (7.37%)6420.0 WDrop High
25 mm²101 A78 A11.86 V (2.86%)403.1 V19.57 V (4.71%)4108.8 WDrop High
35 mm²125 A97 A8.47 V (2.04%)406.5 V13.98 V (3.37%)2934.9 WDrop High
50 mm²151 A118 A5.93 V (1.43%)409.1 V9.78 V (2.36%)2054.4 WDrop High
70 mm²192 A150 A4.24 V (1.02%)410.8 V6.99 V (1.68%)1467.4 WDrop High
95 mm²232 A181 A3.12 V (0.75%)411.9 V5.15 V (1.24%)1081.3 W✓ OK (≤3%)
120 mm²269 A210 A2.47 V (0.6%)412.5 V4.08 V (0.98%)856.0 W✓ OK (≤3%)
150 mm²309 A241 A1.98 V (0.48%)413.0 V3.26 V (0.79%)684.8 W✓ OK (≤3%)
185 mm²353 A275 A1.6 V (0.39%)413.4 V2.64 V (0.64%)555.2 W✓ OK (≤3%)
240 mm²415 A324 A1.24 V (0.3%)413.8 V2.04 V (0.49%)428.0 W✓ OK (≤3%)
300 mm²477 A372 A0.99 V (0.24%)414.0 V1.63 V (0.39%)342.4 W✓ OK (≤3%)
400 mm²570 A445 A0.74 V (0.18%)414.3 V1.22 V (0.29%)256.8 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 200A at 40 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 200A over 40m at 415V (voltage drop: 3.12V or 0.75%).

What is the power capacity of 200A at 415V?

At unity power factor, 200A at 415V supports 143.76 kW with a standard 200A circuit breaker.