40 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 9.88V (2.38%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.78V (2.36%)
Voltage at Load405.1 VLine Loss: 684.8 W
Max Power & Breaker28.75 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.54 V (9.53%)375.5 V65.22 V (15.72%)2739.2 WDrop High
2.5 mm²24 A18 A23.72 V (5.72%)391.3 V39.13 V (9.43%)1643.5 WDrop High
4 mm²32 A25 A14.83 V (3.57%)400.2 V24.46 V (5.89%)1027.2 WDrop High
6 mm²41 A32 A9.88 V (2.38%)405.1 V16.3 V (3.93%)684.8 W✓ OK (≤3%)
10 mm²57 A44 A5.93 V (1.43%)409.1 V9.78 V (2.36%)410.9 W✓ OK (≤3%)
16 mm²76 A59 A3.71 V (0.89%)411.3 V6.11 V (1.47%)256.8 W✓ OK (≤3%)
25 mm²101 A78 A2.37 V (0.57%)412.6 V3.91 V (0.94%)164.4 W✓ OK (≤3%)
35 mm²125 A97 A1.69 V (0.41%)413.3 V2.8 V (0.67%)117.4 W✓ OK (≤3%)
50 mm²151 A118 A1.19 V (0.29%)413.8 V1.96 V (0.47%)82.2 W✓ OK (≤3%)
70 mm²192 A150 A0.85 V (0.2%)414.2 V1.4 V (0.34%)58.7 W✓ OK (≤3%)
95 mm²232 A181 A0.62 V (0.15%)414.4 V1.03 V (0.25%)43.3 W✓ OK (≤3%)
120 mm²269 A210 A0.49 V (0.12%)414.5 V0.82 V (0.2%)34.2 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (0.1%)414.6 V0.65 V (0.16%)27.4 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.08%)414.7 V0.53 V (0.13%)22.2 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.06%)414.8 V0.41 V (0.1%)17.1 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.05%)414.8 V0.33 V (0.08%)13.7 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)414.9 V0.24 V (0.06%)10.3 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 40A at 40 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 40A over 40m at 415V (voltage drop: 9.88V or 2.38%).

What is the power capacity of 40A at 415V?

At unity power factor, 40A at 415V supports 28.75 kW with a standard 40A circuit breaker.