200 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.45V (1.88%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.59V (2.45%)
Voltage at Load23.5 VLine Loss: 90.1 W
Max Power & Breaker4.8 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (118.89%)0.0 V47.07 V (196.11%)5706.7 WDrop High
2.5 mm²24 A18 A17.12 V (71.33%)6.9 V28.24 V (117.67%)3424.0 WDrop High
4 mm²32 A25 A10.7 V (44.58%)13.3 V17.65 V (73.54%)2140.0 WDrop High
6 mm²41 A32 A7.13 V (29.72%)16.9 V11.77 V (49.03%)1426.7 WDrop High
10 mm²57 A44 A4.28 V (17.83%)19.7 V7.06 V (29.42%)856.0 WDrop High
16 mm²76 A59 A2.67 V (11.15%)21.3 V4.41 V (18.39%)535.0 WDrop High
25 mm²101 A78 A1.71 V (7.13%)22.3 V2.82 V (11.77%)342.4 WDrop High
35 mm²125 A97 A1.22 V (5.1%)22.8 V2.02 V (8.4%)244.6 WDrop High
50 mm²151 A118 A0.86 V (3.57%)23.1 V1.41 V (5.88%)171.2 WDrop High
70 mm²192 A150 A0.61 V (2.55%)23.4 V1.01 V (4.2%)122.3 WDrop High
95 mm²232 A181 A0.45 V (1.88%)23.5 V0.74 V (3.1%)90.1 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (1.49%)23.6 V0.59 V (2.45%)71.3 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (1.19%)23.7 V0.47 V (1.96%)57.1 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.96%)23.8 V0.38 V (1.59%)46.3 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.74%)23.8 V0.29 V (1.23%)35.7 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.59%)23.9 V0.24 V (0.98%)28.5 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.45%)23.9 V0.18 V (0.74%)21.4 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 200A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 200A over 5m at 24V (voltage drop: 0.45V or 1.88%).

What is the power capacity of 200A at 24V?

At unity power factor, 200A at 24V supports 4.8 kW with a standard 200A circuit breaker.