200 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 0.71V (2.97%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.59V (2.45%)
Voltage at Load23.3 VLine Loss: 142.7 W
Max Power & Breaker4.8 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.07 V (237.78%)0.0 V94.13 V (392.22%)11413.3 WDrop High
2.5 mm²24 A18 A34.24 V (142.67%)0.0 V56.48 V (235.33%)6848.0 WDrop High
4 mm²32 A25 A21.4 V (89.17%)2.6 V35.3 V (147.08%)4280.0 WDrop High
6 mm²41 A32 A14.27 V (59.44%)9.7 V23.53 V (98.06%)2853.3 WDrop High
10 mm²57 A44 A8.56 V (35.67%)15.4 V14.12 V (58.83%)1712.0 WDrop High
16 mm²76 A59 A5.35 V (22.29%)18.6 V8.82 V (36.77%)1070.0 WDrop High
25 mm²101 A78 A3.42 V (14.27%)20.6 V5.65 V (23.53%)684.8 WDrop High
35 mm²125 A97 A2.45 V (10.19%)21.6 V4.03 V (16.81%)489.1 WDrop High
50 mm²151 A118 A1.71 V (7.13%)22.3 V2.82 V (11.77%)342.4 WDrop High
70 mm²192 A150 A1.22 V (5.1%)22.8 V2.02 V (8.4%)244.6 WDrop High
95 mm²232 A181 A0.9 V (3.75%)23.1 V1.49 V (6.19%)180.2 W~ ≤5%
120 mm²269 A210 A0.71 V (2.97%)23.3 V1.18 V (4.9%)142.7 W✓ OK (≤3%)
150 mm²309 A241 A0.57 V (2.38%)23.4 V0.94 V (3.92%)114.1 W✓ OK (≤3%)
185 mm²353 A275 A0.46 V (1.93%)23.5 V0.76 V (3.18%)92.5 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (1.49%)23.6 V0.59 V (2.45%)71.3 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (1.19%)23.7 V0.47 V (1.96%)57.1 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.89%)23.8 V0.35 V (1.47%)42.8 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 200A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 200A over 10m at 24V (voltage drop: 0.71V or 2.97%).

What is the power capacity of 200A at 24V?

At unity power factor, 200A at 24V supports 4.8 kW with a standard 200A circuit breaker.