225 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.2V (2.51%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 1.29V (2.68%)
Voltage at Load46.8 VLine Loss: 270.8 W
Max Power & Breaker10.8 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A96.3 V (200.62%)0.0 V158.85 V (330.94%)21667.5 WDrop High
2.5 mm²24 A18 A57.78 V (120.38%)0.0 V95.31 V (198.56%)13000.5 WDrop High
4 mm²32 A25 A36.11 V (75.23%)11.9 V59.57 V (124.1%)8125.3 WDrop High
6 mm²41 A32 A24.07 V (50.16%)23.9 V39.71 V (82.73%)5416.9 WDrop High
10 mm²57 A44 A14.45 V (30.09%)33.6 V23.83 V (49.64%)3250.1 WDrop High
16 mm²76 A59 A9.03 V (18.81%)39.0 V14.89 V (31.03%)2031.3 WDrop High
25 mm²101 A78 A5.78 V (12.04%)42.2 V9.53 V (19.86%)1300.1 WDrop High
35 mm²125 A97 A4.13 V (8.6%)43.9 V6.81 V (14.18%)928.6 WDrop High
50 mm²151 A118 A2.89 V (6.02%)45.1 V4.77 V (9.93%)650.0 WDrop High
70 mm²192 A150 A2.06 V (4.3%)45.9 V3.4 V (7.09%)464.3 WDrop High
95 mm²232 A181 A1.52 V (3.17%)46.5 V2.51 V (5.23%)342.1 W~ ≤5%
120 mm²269 A210 A1.2 V (2.51%)46.8 V1.99 V (4.14%)270.8 W✓ OK (≤3%)
150 mm²309 A241 A0.96 V (2.01%)47.0 V1.59 V (3.31%)216.7 W✓ OK (≤3%)
185 mm²353 A275 A0.78 V (1.63%)47.2 V1.29 V (2.68%)175.7 W✓ OK (≤3%)
240 mm²415 A324 A0.6 V (1.25%)47.4 V0.99 V (2.07%)135.4 W✓ OK (≤3%)
300 mm²477 A372 A0.48 V (1.0%)47.5 V0.79 V (1.65%)108.3 W✓ OK (≤3%)
400 mm²570 A445 A0.36 V (0.75%)47.6 V0.6 V (1.24%)81.3 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 225A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 225A over 15m at 48V (voltage drop: 1.2V or 2.51%).

What is the power capacity of 225A at 48V?

At unity power factor, 225A at 48V supports 10.8 kW with a standard 225A circuit breaker.