25 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 1.0V (2.09%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.06V (2.21%)
Voltage at Load47.0 VLine Loss: 25.1 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A10.7 V (22.29%)37.3 V17.65 V (36.77%)267.5 WDrop High
2.5 mm²24 A18 A6.42 V (13.38%)41.6 V10.59 V (22.06%)160.5 WDrop High
4 mm²32 A25 A4.01 V (8.36%)44.0 V6.62 V (13.79%)100.3 WDrop High
6 mm²41 A32 A2.67 V (5.57%)45.3 V4.41 V (9.19%)66.9 WDrop High
10 mm²57 A44 A1.61 V (3.34%)46.4 V2.65 V (5.52%)40.1 W~ ≤5%
16 mm²76 A59 A1.0 V (2.09%)47.0 V1.65 V (3.45%)25.1 W✓ OK (≤3%)
25 mm²101 A78 A0.64 V (1.34%)47.4 V1.06 V (2.21%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A0.46 V (0.96%)47.5 V0.76 V (1.58%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.32 V (0.67%)47.7 V0.53 V (1.1%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.23 V (0.48%)47.8 V0.38 V (0.79%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.17 V (0.35%)47.8 V0.28 V (0.58%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.13 V (0.28%)47.9 V0.22 V (0.46%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.22%)47.9 V0.18 V (0.37%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.18%)47.9 V0.14 V (0.3%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.14%)47.9 V0.11 V (0.23%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.11%)47.9 V0.09 V (0.18%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.08%)48.0 V0.07 V (0.14%)1.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 25A over 15m at 48V (voltage drop: 1.0V or 2.09%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.